2. Important Safety Warnings
SAVE THESE INSTRUCTIONS
This manual contains important instructions and warnings that should be followed during the installation
and maintenance of all SmartOnline S3M 3-Phase 25kVA, 30kVA, 50kVA, 60kVA, 80kVA and 100kVA UPS
Systems.Failuretoheedthewarningsmayaectyourwarranty.
2.1 UPS Location Warnings
Install the UPS indoors, away from heat, direct sunlight, dust and excess moisture or other conductive contaminants.
Install the UPS in a structurally sound area. The UPS is extremely heavy; take care when moving and lifting the unit.
Only operate the UPS at indoor temperatures between 0° C and 40° C.
Optimum UPS performance and maximum battery life is obtained when the operating temperature is maintained
between 17° C and 25° C.
Ensure the installation area has sucient space for maintenance and ventilation of the UPS system. Maintain a
minimum clearance of 20 in. (500 mm) from the rear and both sides of the UPS and 23.6 in. (600 mm) from the front
for maintenance, access and ventilation.
Do not install the UPS near magnetic storage media, as this may result in data corruption.
2.2 Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to
cause the failure of the life support equipment or to signicantly aect its safety or eectiveness is not recommended.
CAUTION! Risk of electrical shock – Hazardous live parts inside the unit are energized from the external battery
supply even when the input AC power is disconnected from an AC supply.
2.3 Battery Warnings
This UPS contains LETHAL VOLTAGES. The UPS is designed to supply power, even when disconnected from
utility power. Only AUTHORIZED SERVICE PERSONNEL should access the interior of the UPS after disconnecting
utility and DC power.
Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or
replacement should be performed only by qualied service personnel, observing proper precautions. Turn o
the UPS before connecting or disconnecting external batteries. Use tools with insulated handles. Do not open
the batteries. Do not short or bridge the battery terminals with any object.
The batteries are recyclable. Refer to local codes for disposal requirements or visit Tripplite.Eaton.com/support/
recycling-program for recycling information.
Do not dispose of the batteries in a re, mutilate the batteries or open the battery coverings. Escaping electrolytes
may be toxic and cause injury to skin and eyes.
Do not disconnect the batteries while the UPS is in battery mode.
Disconnect the charging source prior to connecting or disconnecting terminals.
The following precautions should be observed:
1) Remove watches, rings and other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and electrical-grade boots.
4) Use an electrical-grade rubber mat while servicing batteries.
5) Do not lay tools or metal parts on top of batteries or battery cabinets.