Haier MVAL036ME2AA 36,000 BTU 3x3 Cassette Indoor Unit

User Manual - Page 18

For MVAL036ME2AA.

PDF File Manual, 72 pages, Read Online | Download pdf file

MVAL036ME2AA photo
Loading ...
Loading ...
Loading ...
18 31-5000473 Rev. 0
ENGLISH
ELECTRICAL WIRING
Wire gauge size and breaker size for total indoor amp draw. Current NEC guidelines and local codes will trump this chart.
• The electrical power line and signal line connections must be tight.
• Every indoor unit must have a ground connection.
• The power wire should be size up if it exceeds the permissible length.
Shielding of the control wire of all the indoor and outdoor units should be connected together and grounded at
one point.
• Signal lines should not exceed 3280ft(1000m).
Wired Controller ABC Chart
• The shielding layer of the controller wire must be grounded at the outdoor unit chassis ground.
• The total length of the controller wire shall not be more than 820ft(250m).
Items Cross Section
AWG (mm²)
Length
in(mm)
Rated Current of
Overflow Breaker
(A)
Rated Current of
Residual Circuit
Breaker(A)
Ground Fault
Interrupter (mA)
Response Time (S)
Cross
Sectional Area
of Signal Line
< 7 14 (2.5) 65.6 (20) 10 10 A, 30 mA, 0.1S or below
16 AWG (1.25mm²)
7 and < 11
12 (4) 65.6 (20) 15 15 A, 30 mA, 0.1S or below
11 and < 16
10 (6) 82 (25) 20 20 A, 30 mA, 0.1S or below
16 and < 22
8 (8) 98.4 (30) 30 30 A, 30 mA, 0.1S or below
22 and < 27
6 (10) 131 (40) 30 30 A, 30 mA, 0.1S or below
Total Current
of Indoor
Units (A)
Length of Controller Wire ft(m)
Wiring Dimensions AWG (mm²)
820 (250)
18 (0.72) x 3 core shielding line
Loading ...
Loading ...
Loading ...