Tripp Lite SVX30KM1P4B SmartOnline SVX Series 30kVA 400/230V 50/60Hz Modular Scalable 3-Phase On-Line Double-Conversion Medium-Frame UPS System, 4 Battery Modules

Owner's Manual - Page 25

For SVX30KM1P4B. Series: SVX Series

PDF File Manual, 148 pages, Read Online | Download pdf file

SVX30KM1P4B photo
Loading ...
Loading ...
Loading ...
25
9. Control Panel
SmartOnline SVX-Series UPS Operating Mode
Standby Bypass Line Battery Battery Test Fault Converter ECO
Time Y Y Y Y Y Y Y Y
Audible Alarm Y Y Y Y Y Y Y Y
Factory Reset Y
EEPROM Reset Y
EPO Function Y
Save Setting Y Y
Table 9.3
9.3.6.2 System
The SETUP – SYSTEM screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table
9.4 for details.
SYSTEM
Output Voltage*
Bypass Setting
Converter Mode
ECO Mode
Auto Restart
Cold Start
Battery Mode Delay Time*
System Shutdown Time*
System Restore Time*
Redundancy*
Charger Test
Bypass Mode
Set output voltage (220/230/240V) (Default: 220V)*
Voltage – Upper limit: +10/15/20%; lower limit: -10/15/20% (Default: +15%/-20%)
Frequency – Upper limit: +1/2/4Hz; lower limit -1/2/4Hz (Default: +/-4Hz)
Set “Disable” or “Enable” (Default: Disabled)
Set “Disable” or “Enable” (Default: Disabled)
Set “Disable” or “Enable” (Default: Enabled)
Set “Disable” or “Enable” (Default: Enabled)
Set “Disable” or “Enable” (Default Enabled). Refer to Section 7.3: Cold Start
Set system shutdown delay time in battery mode (0-9990 sec.)
Set system shutdown time 0.2 – 99 min. (Default: 0.2 min.)
Set system restore time 0-9999 min. (Default: 001)
Total Power – Quantity of Power Modules installed
Redundancy – Quantity of Power Modules to be redundant
Set “Disable” or “Enable” (Default: Disabled)
When this feature is enabled and the DC breaker of the UPS system is off, LCD can
display the charger voltage
Loading ...
Loading ...
Loading ...