6 31-5000587 Rev. 1
ENGLISH
Step 1 - Preparation
Select the Outdoor location:
Choose a level place solid enough to bear the weight
and vibration of the OD unit and where the operation
noise will not be amplified.
Choose a location where the hot air discharge and/or
noise will not create a nuisance for neighbors.
Ensure there is sufficient space to maneuver the OD
unit into place.
Ensure there is sufficient space and no obstructions
for the air inlet and outlet.
• I nstall the unit’s power/communication wiring at
least 10 feet away from television and radio sets to
prevent interference.
Ensure any moisture sensitive items are kept away
from the condensate drain path of the OD unit.
NOTES:
OD unit cannot hang from a ceiling or be stacked.
Ensure that accumulated snow and debris will not
block the air inlet or the coil if installing the outdoor
unit with a fence or guard rail around it.
Ensure ventilation in case of refrigerant leakage.
R-410A is a safe, nontoxic, and nonflammable
refrigerant.
Avoid installing the OD unit where corrosive gases,
such as sulfur oxides, ammonia, and sulfurous gas
are produced. Consult with an installation specialist
about using a corrosion-proof or anti-rust additive to
protect the unit coils.
INSTALLATION INSTRUCTIONS
(3) Installation and maintenance space
Selection of installation location of outdoor
Above
12(300)
Above 40 (1000)
Above
16(400)
Above
16(400)
Above
16(400)
Above16(400) Above16(400)
Above80(2000)
Above12(300)
Above 40(1000)
Above 177(4500)
Above
24(600)
If wall is half the height of the unit, 8 (250).
If wall is between half the height of the unit and
the same height of the unit, 12 (300)
If wall is half the height of the unit, 8 (250).
If wall is between half the height of the unit and the same
height of the unit, 12 (300)