3. Installation and Wiring
3.8.3 Over-Current Protection
CAUTION!
Wiring must be performed by qualied professional personnel.
Before wiring or making any electrical connection, ensure the power supplied to the input and output of the UPS is cut
o completely and the internal battery connectors are disconnected.
When connecting the UPS to the utility AC power and bypass source, protective devices and 3-pole connectors
must be installed. The protective devices and 3-pole contactors must use approved components that meet safety
certications. The thermo-magnetic circuit breakers should be IEC 60947-2 trip curve C (normal). Refer below for
required protective devices:
25kVA UPS: 100A input circuit breaker required.
30kVA UPS: 125A input circuit breaker required.
50kVA UPS: 200A input circuit breaker required
60kVA UPS: 250A input circuit breaker required
80kVA UPS: 320A input circuit breaker required
100kVA UPS: 400A input circuit breaker required
When connecting the critical loads to the UPS, a listed certied breaker must be installed between them. Refer to the
below for the required breakers:
25kVA UPS: 100A input circuit breaker required.
30kVA UPS: 125A input circuit breaker required.
50kVA UPS: 200A input circuit breaker required
60kVA UPS: 250A input circuit breaker required
80kVA UPS: 320A input circuit breaker required
100kVA UPS: 400A input circuit breaker required
• Check that the size, diameter, phase and polarity of each cable connecting to the UPS is correct. For the specications
of input/output cables, refer to the table in section 3.10.1 Power Cables.
3.9 UPS to Battery Cabinet Model Compatibility
Battery Cabinets
with Batteries
BP240V09 /
09K BP240V40 BP240V40L BP240V65 BP240V65L BP240V100 BP240V100L
Battery Cabinets
with NO Batteries
BP240V09-
NIB
BP240V40-
NIB
BP240V40L-
NIB
BP240V65-
NIB
BP240V65L-
NIB
BP240V100-
NIB
BP240V100L-
NIB
S3M25K, S3M30K No Yes Yes Yes Yes Yes No
S3M50K No No Yes Yes Yes Yes Yes
S3M60K No No No No Yes Yes Yes
S3M80K, S3M100K No No No No Yes No Yes
Note: For battery cabinet breaker information, refer to the Owner’s Manual for your battery cabinet.