10. Specifications
Specifications are subject to change without further notice.
Model SMART600PSGLCD SMART1000PSGLCD SMART1200PSGLCD SMART1500PSGLCD
Nominal voltage and
input range
120V~, 97-145V 120V~, 97-145V 120V~, 97-145V 120V~, 97-145V
Nominal input frequency
and tolerance
50/60 Hz (Frequency
low/comeback:
45/47Hz±0.2Hz;
or 55/57Hz±0.2Hz;
Frequency high/
comeback:
55/53Hz±0.2Hz;
65/63Hz±0.2Hz)
50/60 Hz (Frequency
low/comeback:
45/47Hz±0.2Hz;
or 55/57Hz±0.2Hz;
Frequency high/
comeback:
55/53Hz±0.2Hz;
65/63Hz±0.2Hz)
50/60 Hz (Frequency
low/comeback:
45/47Hz±0.2Hz;
or 55/57Hz±0.2Hz;
Frequency high/
comeback:
55/53Hz±0.2Hz;
65/63Hz±0.2Hz)
50/60 Hz (Frequency
low/comeback:
45/47Hz±0.2Hz;
or 55/57Hz±0.2Hz;
Frequency high/
comeback:
55/53Hz±0.2Hz;
65/63Hz±0.2Hz)
Nominal output voltage: 120V~ in line mode and
120V~ battery
120V~ in line mode and
120V~ battery
120V~ in line mode and
120V~ battery
120V~ in line mode and
120V~ battery
Nominal output frequency 50/60 Hz (50Hz ±2% /
60Hz ±1.67%)
50/60 Hz (50Hz ±2% /
60Hz ±1.67%)
50/60 Hz (50Hz ±2% /
60Hz ±1.67%)
50/60 Hz (50Hz ±2% /
60Hz ±1.67%)
Output voltage regulation
in line mode
120V~ (±10%) 120V~ (±10%) 120V~ (±10%) 120V~ (±10%)
Output voltage regulation
in battery mode
120V~ (±10%) 120V~ (±10%) 120V~ (±10%) 120V~ (±10%)
Nominal output power
in W / VA
360W / 600VA 600W / 1000VA 720W / 1200VA 900W / 1500VA
Output voltage waveform Sinusoidal in line mode
and Sinusoidal in battery
mode
Sinusoidal in line mode
and Sinusoidal in battery
mode
Sinusoidal in line mode
and Sinusoidal in battery
mode
Sinusoidal in line mode
and Sinusoidal in battery
mode
Maximum output current
@ P. F.
5A @ 120V~ 8.3A @ 120V~ 10A @ 120V~ 12A @ 120V~
Maximum output P.F. P.F. = 0.6
Efficiency with nominal
load
96% 96% 96% 96%
Efficiency at rated load 96% 96% 96% 96%
Maximum operating
altitude at 100% of
nominal power
9842 ft. (3000 m) 9842 ft. (3000 m) 9842 ft. (3000 m) 9842 ft. (3000 m)
Online overload capability 110%+15%/-5% for 5
minutes; 120%+15%/-
5% immediately and go
to fault
110%+15%/-5% for 5
minutes; 120%+15%/-
5% immediately and go
to fault
110%+15%/-5% for 5
minutes; 120%+15%/-
5% immediately and go
to fault
110%+15%/-5% for 5
minutes; 120%+15%/-
5% immediately and go
to fault
Overload capacity in
battery mode
110%+15%/-5% for 10
seconds; 120%+15%/-5%
Shutdown immediately
110%+15%/-5% for 10
seconds; 120%+15%/-5%
Shutdown immediately
110%+15%/-5% for 10
seconds; 120%+15%/-5%
Shutdown immediately
110%+15%/-5% for 10
seconds; 120%+15%/-5%
Shutdown immediately
Current limitation: 10A @ 120V~ 10A @ 120V~ 10A @ 120V~ 15A @ 120V~
Autonomy time at full
load
2.5 minutes @ 360W 2 minutes @ 600W 2.5 minutes @ 720W 3 minutes @ 900W
Battery recharge time 7 hours 7 hours 7 hours 7 hours
Transfer time 6ms Typical, 10ms Max 6ms Typical, 10ms Max 6ms Typical, 10ms Max 6ms Typical, 10ms Max
Outlets 4x 5-15R outlets with
battery backup and surge;
4x 5-15R outlets surge
only
4x 5-15R outlets with
battery backup and surge;
4x 5-15R outlets surge
only
5x 5-15R outlets with
battery backup and surge;
5x 5-15R outlets surge
only
5x 5-15R outlets with
battery backup and surge;
5x 5-15R outlets surge
only
Maximum input current 5A @ 120V~ 8.3A @ 120V~ 10A @ 120V~ 12A @ 120V~
Loading ...