24
Battery
Battery
Positive Voltage (V)
Negative Voltage (V)
Positive Current (A)
Negative Current (A)
Remain Time (Min)
Capacity (%)
Test Result
Charging Status
9.3.6 Setup Screen
Use “Down/Right” key to select “Setup” option. A password is required to access the menu sub-screen. Default password is 0000.
PRE-ALARM
BATTERY
SYSTEM
GENERAL
HOME
MENU
SETUP
Enter Password
9.3.6.1 General
The SETUP – GENERAL screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to
table 9.3 for details. The Maintenance password (9999) is required for settings marked with *.
GENERAL
Time*
Change Password
Audible Alarm
Factory Reset*
EEPROM Reset*
EPO Function*
Save Setting*
9. Control Panel
Battery positive voltage, Units 0.1V
Battery negative voltage, Units 0.1V
Battery positive current, Units 0.1A
Battery negative current, Units 0.1A
Battery runtime remaining, Units 1 minute
Percentage of battery capacity remaining, Units 1%
Battery test result
Battery charging status (settable per section 9.3.4 Control Screen)
Set current time / system install date / system latest maintenance date / battery install
date / battery latest maintenance date
Set new password
Set “Disable” or “Enable” (default: Enabled)
Restore to factory default settings
Set EEPROM default
Set EPO “Normal Close Active” or “Normal Open Active”; Default: Normal Open Active
Save EEPROM setting