11
Installing the decorated panel on the body of indoor unit:
receiving window for remote control
the lamp will not ash when wired controller is used
Prior to attaching the panel to the unit locate the louver motor connector on
the panel and the unit. Orientate the panel so they can connect.
First temporarily position it with screws.
Tighten each screw a little at a time to allow the panel to seat ush against the unit.
If the foam gasket does not seal against the unit then lower the body of the indoor unit.
Wiring of panel:
Connect both connections for the display and louver motors.
Attention
If the panel does not seal against the unit then leaking air could
cause moisture to condense on ceiling surfaces and cause
water damage.
Unit must be level to prevent water from leaking from the condensate pan.
Fig.1
any gap is not allowed
Fig.2
air leakage
Water damage
Condensing
moisture
side of decorated board
side of indoor unit
Inaccurate board location
(may vary)
Installation Procedures