the condensation either to the factory supplied condensate bottle, or to a drain or other
location as required by the application. The internal pump is rated at 20 foot of head
pressure. This means it can pump water to a maximum of 20 feet vertically. Each pump
is equipped with an overflow safety cut-off that automatically shuts your KPHP unit
down, sounds an audible alarm and displays a fault code (CP). This prevents accidental
flooding of the conditioned space.
Condensate Tank & High Level Alarm - All KPHP models come standard with an
external condensate tank. The tank is equipped with an overflow safety cut-off. When
the tank is full, the safety will automatically shut down your KPHP systems, sound an
audible alarm and display a fault code (CF) This prevents accidental flooding of the
conditioned space. If you are using the supplied bypass plug and not using the tank this
alarm is nonfunctional.
Service Ports - Located in the filter access compartment in the front of your KwiKool
below the control panel. This gives service personal a connection point for service
gauges to monitor the operating pressures of your KwiKool KPHP refrigeration system.
Sight Glass/Moisture Indicator - Located in the discharge air make up inlet. This
feature allows operators and service personal to view the condition of the refrigerant
returning to the evaporator coil. Used as a diagnostic tool by qualified personal.
G.
H.
I.
Page 10
VI / Application Requirements
Air Temperature Requirements Cooling - The environmental requirements of
your KwiKool unit at the installation site are 60 to 110 degrees F for the condenser
make up air located on the front inlet on the top of the unit. If the unit is operated in an
environment above 110 F the high pressure switch may trip, stopping the unit’s
compressor. You also may notice diminished performance. The High Pressure Switch
type is a manual reset. The reset switch is located in the Return Air grill filter compart-
ment. Reset the unit by pressing the button labeled HP Reset. Standard air-cooled
KwiKool models are not designed to operate at temperatures below 60 degrees F. in
cooling mode. Low-ambient temperature controls must be special ordered at an
additional cost. Temperatures below 60 degrees F will cause the discharge air exhaust
fan to cycle excessively and may damage the fan cycling switch, which requires
qualified service personal to repair and can void your warranty.
Air Temperature Requirements Heating - The environmental requirements of
your KwiKool unit at the installation site are 40 to 80 degrees F for the supply air
located on the front of the unit. If the unit is operated in an environment above 80 F
the high pressure switch may trip, stopping the unit’s compressor. You also may notice
diminished performance. The High Pressure Switch type is a manual reset. The reset
switch is located in the Return Air grill filter compartment. Reset the unit by pressing
the button labeled HP Reset. Standard air-cooled KwiKool models are not designed to
operate at temperatures below 40 degrees F. in heat mode. Temperatures below 40
degrees F will cause the supply air fan to cycle excessively and may damage the fan
cycling switch, which requires qualified service personal to repair and can void your
warranty.
Capacity & Temperature Settings - Sizing of our units is based on matching
capacity to a specific heat load while maintaining a 72 degree F temperature. In order
to maintain temperatures at 72 degrees F, the unit must have correctly sized capacity.