1. Refrigerator
5) Startup/Cool Down–MH, PH, and TXVH energize. There is a slight delay, Comp,
ConFM, and EvapFM energize. On PT2A and R_2A, MH and BH also energize. Cabinet
temperature appears on display and 2-hr. defrost timer starts. Note: If DTh is above
50°F (10°C) EvapFM is de-energized.
a) MH Diagnosis: MH energizes at startup (except PT2A). If 115VAC is present,
check amp draw of MH. If an amp reading is not present, check the continuity of
MH. If defective, replace MH. Note: MH energizes and de-energizes with Comp and
CondFM on PT2A and R_2A models.
b) BH Diagnosis: BH energizes at startup on R_1A and with Comp on R_2A.
If 115VAC is present, check amp draw of BH. If an amp reading is not present, check
the continuity of BH. If defective, replace BH. Note: BH energizes and de-energizes
with Comp and CondFM on R_2A models.
c) TXVH (if applicable) Diagnosis: Conrm amp draw of TXVH. If no amp draw
available, check for 115VAC at TXVH grey wire (GY) to neutral (W). If 115VAC is
not present, check wiring connections to TXVH. If 115VAC is present, check TXVH
continuity. If open, replace TXVH.
d) EvapFMDiagnosis: Conrm that EvapFM(s) energize. If not, conrm DTh is at
50°F (10°C) or lower, doors are closed and DS engaged, check DS continuity.
If DTh is above 50°F (10°C), wait for evaporator to cool down. If DS is engaged and
contacts are open, replace DS. If DS is engaged and contacts are closed, check for
115VAC at CM 5 (F) dark blue (DBU) wire to neutral white (W) wire. If 115VAC is not
present, replace CM. If 115VAC is present, check EvapFM blades for binding and
EvapFM continuity.
e) Solid Door Cabinet Light Diagnosis: LED(s) are activated from door switch.
Open the door (upper on HS/HG), conrm LED(s) energizes. If not, with door open,
check for 5 to 12VDC at CM S4 brown (BR) to CM S4 blue (BU). If 5 to 12VDC
is not present at CM S4 brown (BR) to CM S4 blue (BU), conrm 115VAC power
supply to CM at terminals 2 (L) black (BK) to 3 (N) white (W). If 115VAC is present,
and LED(s) are off, check DS continuity. If DS is disengaged (open) and contacts
are closed, replace DS. IfDS is disengaged (open) and contacts are open, check
for 115VAC from CM 6 (LED) (Y) to a neutral (W). If 115VAC is not present, replace
CM. If 115VAC is present at CM 6 (LED) (Y) to a neutral (W) and LED(s) are not
on, check for 24VDC at DCD black (BK) wire to DCD red (R) wire. If 24VDC is not
present, check continuity of DCD driver. If open, replace DCD driver. If 24VDC is
present and LED(s) are not on, check wiring harness and wiring connections from
DCD to LED(s). Ifconnections are good and LED(s) are not on, replace LED(s).