Specifications
Model OMNI650LCD OMNI900LCD
Nominal voltage and input
range
120V~, 89-139V~ 120V~, 89-139V~
Nominal input frequency and
tolerance
60 Hz (+/- 5 Hz) 60 Hz (+/- 5 Hz)
Nominal output voltage 120V~ in line mode and
115V~ in battery
120V~ in line mode and
115V~ in battery
Nominal output frequency 60 Hz (+/-0.5 Hz) 60 Hz (+/-0.5 Hz)
Output voltage regulation in
line-mode
120V~ (+14%) 120V~ (+14%)
Output voltage regulation in
battery mode
120V~ (+/-5%) 120V~ (+/-5%)
Nominal output power in
W / VA:
350W / 650VA 475W / 900VA
Output voltage waveform Sinusoidal in line mode and
quasi-sine (PWM) in battery
mode
Sinusoidal in line mode and
quasi-sine (PWM) in battery
mode
Maximum output current @ P.F. 5.4A @ 120V~ 7.5A @ 120V~
P.F. = 0.5 P.F. = 0.5
Efficiency with nominal load 97% 97%
Maximum operating altitude at
100% of nominal power
6561 ft. (2000 m) 6561 ft. (2000 m)
Online overload capability 125% @ 10 minutes 125% @ 10 minutes
Overload capacity in battery
mode
105% @ 0.5 seconds 105% @ 0.5 seconds
Autonomy time at full load 3.2 minutes @ 350W 3.57 minutes @ 475W
Battery recharge time 20 hours 16 hours
Transfer time 3 milliseconds typical (4
milliseconds max)
3 milliseconds typical (4
milliseconds max)
Outlets 4x 5-15R outlets with
battery backup, regulation
and surge; 4x 5-15R outlets
surge only)
4x 5-15R outlets with
battery backup, regulation
and surge; 4x 5-15R outlets
surge only)
Maximum input current 12A 12A