AmeriKooler QC060872**N Quick Ship Indoor Walk-In Cooler

Installation manual for pro3 - Page 7

For QC060872**N.

PDF File Manual, 36 pages, Download pdf file

Loading ...
Loading ...
Loading ...
7
Table 1: Control Factory Default Settings
Indoor
Models
Temperature
Set Points
Defrost
Start Times
Defrost Duration
(Maximum)
Drip
Time
Fan
Delay
Defrost Termination
Set Point
EZY
Default
M - Cooler Models
Air Defrost
38˚F 4 / day 60 min. 38˚F 3
M - Cooler Models
Electric Defrost
34˚F 4 / day 40 min. 2 min. 1 min. 65˚F 2
L - Freezer Models
Electric Defrost
-10˚F 4 / day 40 min. 2 min. 1 min. 65˚F 1
12. Connect unit to power supply using the cord with plug,
if provided, or hard wire. Adhere to local electrical/
wiring codes.
IMPORTANT:
Do not use extension cords to connect unit to power.
Plug-in to grounded three prong outlet.
Do not remove grounding prong.
Do not use a power adapter.
13.
Apply power to unit. All controls are preset to factory
default settings (See Table 1).
14. Check unit for proper operation.
15. To change defaults as a group follow steps mentioned
in the next section:
CHANGING THE EZY
To change defaults as a group, follow these steps:
1.
Press Set button and hold in until the display flashes “PS”.
2. Press the Set Button and the display will change to “0”
and will begin to flash.
3. Press the up button until “22” is displayed.
4. Press the Set button.
5. Press the down button 2 times. “EZY” will be displayed.
6. Press the Set button.
7. Select the proper number for the model needed by
1 - L Low temperature model
2 - M Med temperature model - Electric Defrost
3 - M Med temperature model - Air Defrost
8.
Press Set and wait for unit to return out of
programming mode.
9. Disconnect power
10. Press the Set Button while turning unit On
11. “CE” should display to verify programming display.
10. Install the trim around the inside opening with the
hardware provided.
11. Add water to the condensate drain line to maintain liquid
seal in the P-Trap