The recommended installation creates a separate return for the B70DHV in a central area of the
structure. Duct the supply of the unit to the air supply of the existing HVAC system. Connect an insulated
duct from outside to provide fresh make-up air (optional).
DUCTING TO HVAC SYSTEMS
CAUTION!CAUTION!
DO NOT CONNECT WITH A STATIC PRESSURE GREATER THAN OR EQUAL TO +0.5 WG.
CONTACT TECHNICAL SUPPORT AT (800) 558-1711 FOR ADDITIONAL DETAILS.
Ducting Considerations:
All exible ducting connected to the B70DHV should be UL listed.
A short piece of exible ducting on all B70DHV duct connections is recommended to reduce noise and
vibration transmitted to rigid ductwork in the structure.
Use a minimum 8" diameter round or equivalent rectangular duct for total duct lengths of up to 25'. Use a
minimum 10" diameter or equivalent for longer lengths.
• Grills or diusers on the duct ends must not excessively restrict airow.
A length of 8" or more of insulated ex duct or any other vibration isolating material on the outlet of the
B70DHV will reduce air noise from the blower.
Eective dehumidication may require that ducting be branched to isolated, stagnant air ow areas. When
ducting to two or three areas, use 6" or larger diameter branch ducting. When ducting to four or more
areas, use 4"-6" or larger diameter branch ducting. Provisions must be made to provide airow from
supply locations to the central return location. Proper air distribution is important to ensure even humidity
control and heat distribution throughout the structure.
• DO NOT locate the return in a bathroom or a kitchen.