Tripp Lite PDU3EVN10L2130B 10kW 200-240V 3PH Monitored PDU - LX Interface, Gigabit, 48 Outlets, NEMA L21-30P, LCD, 3 m Cord, 0U 1.8 m Height, TAA

Owner’s Manual - Page 9

For PDU3EVN10L2130B. Also, The document are for others Tripp Lite models: PDU3EVN3L2130, PDU3EVN10L2130, PDU3EVN3L2120, PDU3EVN6L2120, PDU3EVN10L2120, PDU3EVN6L2130, PDU3EVSR6G60A, PDU3EVSR6H50A, PDU3EVN6G30B, PDU3EVN10G30B, PDU3EVN3G60B, PDU3EVN6G60B, PDU3EVN10G60B, PDU3EVN3H50B, PDU3EVN6H50B, PDU3EVN6H50BA, PDU3EVN10H50B, PDU3EVN3L1520, PDU3EVN6L1520, PDU3EVN10L1520, PDU3EVN3L1530B, PDU3EVN6L1530B, PDU3EVN10L1530B, PDU3EVN3L2130B, PDU3EVN6L2130B, PDU3EVN2, PDU3EVN6G60C, PDU3EVSR6H50, PDU3EVSR10H50, PDU3EVSR6L1530, PDU3EVSR10L1530, PDU3EVSR6L2130, PDU3EVSR6G60, PDU3EVSR10L2130, PDU3EVS6H50, PDU3EVS6L2130, PDU3EVS6L2120, PDU3EVSR6L2120, PDU3EVSR6L1520, PDU3XEVN6G20, PDU3XEVSR6G20, PDU3XEVSR6G30A, PDU3XEVSR6G30B, PDU3XEVSR6G32A, PDU3XEVSR6G32B, PDU3XEVSR6G60A, PDU3XEVSR6G60B, PDU3XEVSR6G63A, PDU3XEVSR6G63B, PDU3XEVSR6L230B, PDU3XEVSR6L2230, PDU3XEVSRHWA, PDU3XEVSRHWB

PDF File Manual, 18 pages, Read Online | Download pdf file

PDU3EVN10L2130B photo
Loading ...
Loading ...
Loading ...
A B
Remove Access Plate Screws
Ground Terminal
X
Y
Z
N
2-2B
C
9
Installation
Channel the wire through the conduit and insert into the terminal block at locations A, Y, Z,
and N. Secure wires then tighten the screws using a slotted screwdriver and apply a torque of
2.3 N·m (20 in·lb) to each screw. Secure the ground wire to the ground stud and tighten nut.
Connect the conduit to the disconnect device and secure the connector.