Tripp Lite BP240V40 series ±120VDC External Battery Cabinet

Owner's Manual - Page 21

For BP240V40. Also, The document are for others Tripp Lite models: BP240V09, BP240V09K, BP240V09-NIB, BP240V40-NIB, BP240V40L, BP240V40L-NIB

PDF File Manual, 224 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
21
5. Installation
7. Place the cabinet on a level surface as close as
possible to its nal position.
8. Move the cabinet into its nal operating position.
Adjust one front foot to level and immobilize the
unit, then adjust the other support foot accordingly
to ensure the unit is level.
5.2SelectingInstallationPosition
Select a proper environment to install the unit, in order to minimize the possibility of damage to the battery system and
maximize the life of the batteries.
1. Do not block air ow to the ventilation openings of the unit.
2. Ensure environmental conditions of the installation site are in accordance with the unit specications to avoid
overheat and excessive moisture. Refer to section 4.2 Physical Requirements.
3. Do not place the unit in a dusty or corrosive environment or near any ammable objects.
4. The unit is not designed for outdoor use.
Notes:
Place the battery cabinet in a clean, stable environment. Avoid vibration, dust, humidity, ammable gases, liquids and corrosives.
To help prevent high temperatures in the room where the UPS is installed, extractor fans and/or cooling systems are
recommended.
Batteries should be mounted in an environment where the temperature is within the required specications. Temperature is a key
factor in determining battery life and capacity. Battery temperature should be maintained between 59°F to 77°F (20°C to 25°C).
Keep batteries away from heat sources, main air ventilation areas, etc.
WARNING!
Typicalbatteryperformancedatareectsanoperatingtemperaturebetween59°Fto77°F(20°C
to25°C).OperatingtheUPSabovethisrangewillreducethebatterylife,whileoperatingtheUPS
below this range will reduce battery capacity.
If the UPS will not be installed immediately, it must be stored in a room without excessive heat or humidity.