5. Installation
7. Place the cabinet on a level surface as close as
possible to its nal position.
8. Move the cabinet into its nal operating position.
Adjust one front foot to level and immobilize the
unit, then adjust the other support foot accordingly
to ensure the unit is level.
5.2SelectingInstallationPosition
Select a proper environment to install the unit, in order to minimize the possibility of damage to the battery system and
maximize the life of the batteries.
1. Do not block air ow to the ventilation openings of the unit.
2. Ensure environmental conditions of the installation site are in accordance with the unit specications to avoid
overheat and excessive moisture. Refer to section 4.2 Physical Requirements.
3. Do not place the unit in a dusty or corrosive environment or near any ammable objects.
4. The unit is not designed for outdoor use.
Notes:
• Place the battery cabinet in a clean, stable environment. Avoid vibration, dust, humidity, ammable gases, liquids and corrosives.
• To help prevent high temperatures in the room where the UPS is installed, extractor fans and/or cooling systems are
recommended.
• Batteries should be mounted in an environment where the temperature is within the required specications. Temperature is a key
factor in determining battery life and capacity. Battery temperature should be maintained between 59°F to 77°F (20°C to 25°C).
Keep batteries away from heat sources, main air ventilation areas, etc.
WARNING!
Typicalbatteryperformancedatareectsanoperatingtemperaturebetween59°Fto77°F(20°C
to25°C).OperatingtheUPSabovethisrangewillreducethebatterylife,whileoperatingtheUPS
below this range will reduce battery capacity.
• If the UPS will not be installed immediately, it must be stored in a room without excessive heat or humidity.