17
Installation Instructions
The condensate drains from the outdoor unit when the unit operates in heating mode. In
order not to disturb your neighbor and protect the environment, install a drain port and
a drain hose to direct the condensate water. Just install the drain port and rubber washer
to the chassis of the outdoor unit, then connect a drain hose to the port as the right figure
demonstrates.
Outdoor Unit Installation
Drain hose
(prepared by user)
Washer
Drain port
Rubber pad (optional)
Place under the leg pedestal
2. Install Ground Pad or Wall Hangers
1. Install Condensate Drain for Outdoor Unit
1.Determine proper location for outdoor unit.
2.Follow all instructions provided by manufacturer for installing wall hangers
rubber pad.
3.Verify the wall hangers or rubber pad can safely support the weight of the
outdoor unit.
4.Verify the wall hangers or rubber pad is level and meets all outdoor
dimensional clearance.
5.Fix with bolts and nuts tightly on a flat and strong floor.
If installed on the wall or roof, make sure to fix the supporter well to prevent it
from shaking due to serious vibration or strong wind.
WARNING
Florida wind load requirements state that outdoor unit must be anchored to
concrete pad using four 3/8-in diameter power wedge bolt plus(or equivalent)
with 1-in diameter fender washers. Anchor bolts must be embedded into
3000 PSI minimum concrete at a distance of 4 1/2- in from any concrete edge.
The concrete thickness must exceed 1.5 times the anchor depth.