Tripp Lite S3M30K-30K4T 3-Phase 208V UPS + Input Isolation Transformer Kit - 480V Delta to 208V Wye, 30kVA/kW, External Batteries Required

Owner's Manual - Page 21

For S3M30K-30K4T. Also, The document are for others Tripp Lite models: S3M25K*, S3M30K*, S3M50K*, S3M60K*, S3M80K*, S3M100K*

PDF File Manual, 240 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
21
3. Installation and Wiring
3.6 LCD Control Panel, LEDs and Alarms
3.6.1 Introduction: LCD Display
For detailed information on LCD control panel functions, refer to sections 4.3.2 LCD Control Panel Introduction and
4.3.3 Main Page: Default Display.
1
Alarm LED
2
Bypass LED
3
Battery LED
4
Inverter LED
5
EPO Button (the button must be pressed for at least
3 seconds to activate EPO)
6
Touchscreen LCD Screen, 5 in. (127 mm)
3.6.2 Introduction: Audible Alarms and LEDs
Audible Alarms Display LEDs
Alarm Status
Mutable
On/O?
Alarm Bypass Battery Inverter
UPS Initialization Beeps, Once No Flashes/0.5s Flashes/0.5s Flashes/0.5s Flashes/0.5s
UPS Online Mode (Normal) No Beeps No Beeps O O O On
UPS Battery Mode Beeps/2s Yes O O On O
UPS Battery Test Mode No Beeps No Beeps O O On O
UPS ECO Mode No Beeps No Beeps O On O O
UPS Standby Mode No Beeps No Beeps O O O O
UPS Static Bypass Mode No Beeps No Beeps O On O O
UPS Maintenance Bypass Mode No Beeps No Beeps O On O O
UPS Frequency Converter Mode No Beeps No Beeps O O O On
UPS Load Overload Beeps/1s Yes O O O Flashes/2s
UPS Warnings Beeps/2s or Beeps/1s Yes Flashes/2s Flashes/2s O On
UPS Faults Beeps/2s or Beeps/1s Yes On On O O
1
5
2
6
3
4
Loading ...
Loading ...
Loading ...