Horizon Elite 1010/1410 Self-Contained (50 Hz and 60 Hz) 13
Refrigeration charge
All service on refrigeration systems must be performed in accordance with all federal, state and local laws. It is the
responsibility of the technician to ensure that these requirements are met. Recharging ice machine to other than
factory specications will void the warranty.
Ice machine charge specications
Charge Refrigerant type
HCE1010A 24 oz (680 g) R449A
HCE1010W 21 oz (595 g) R404A
HCE1410A 29 oz (822 g) R404A
HCE1410W 21 oz (595 g) R404A
HCC1010A 33 oz (936 g) R404A
HCC1010W 18 oz (510 g) R404A
HCC1410A 35 oz (992 g) R404A
HCC1410W 18 oz (510 g) R404A
HCC1010W Marine 15 oz (425 g) R449A
HCC1410W Marine 15 oz (425 g) R449A
Refrigerant replacement requirements
1. Non-contaminated refrigerant removed from any Follett refrigeration system can be recycled and returned to
the same system after completing repairs. Recycled refrigerant must be stored in a clean, approved storage
container. If additional refrigerant is required, virgin or reclaimed refrigerant that meets ARI standard 700-88
must be used.
2. In the event of system contamination (for example, a compressor burn out, refrigerant leak, presence of
non-condensibles or moisture), the system must be repaired, evacuated and recharged using virgin or
reclaimed refrigerant that meets ARI standard 700-88.
3. Follett Corporation does not approve of recovered refrigerants. Improper refrigeration servicing procedures
will void the factory warranty.
Evacuation
Evacuate the system to a level of 500 microns. When the 500 micron level is reached, close all valves. Allow the
system to sit for approximately 20 minutes. During this period the system pressure should not rise. If the system
pressure rises and stabilizes there is moisture in the system and further evacuation is needed. If the pressure
continues to rise check the system for leaks.
Ambients Minimum Maximum
Air temperature* 50 F/10 C 100 F/37.8 C
Water temperature
45 F/7 C 90 F/32.2 C
* Ambient air temperature is measured at the air-cooled condenser coil inlet.
Ambient water temperature is measured in the ice machine water reservoir.