9. Control Panel
9.3.5 Measurement Screen
Use “Down/Right” key to select “MEASUREMENT” option. Press “Enter” key to enter Control sub-menu. Select Master #00 (the module ID
number as defined in table 7.1) to view Input, Output, Bypass, Load and Battery status for each module.
Battery
Load
Bypass
Output
Input
HOME
MENU
MEASUREMENT
Master #00
STS #
System ID
Input
L-N Voltage (V)
Frequency (Hz)
Input
Output
Output
L-N Current (A)
L-N Voltage (V)
Frequency (Hz)
Power Factor
Bypass
Bypass
L-N Voltage (V)
Frequency (Hz)
Power Factor
Load
Load
S Out (kVA)
P Out (kW)
Load Level (%)
Input phase voltage (L1, L2, L3), Unit 0.1V
Input frequency (L1, L2, L3), Unit 0.1Hz
Output phase voltage (L1, L2, L3), Units 0.1V
Output phase current (L1, L2, L3), Units 0.1A
Output frequency (L1, L2, L3), Units 0.1Hz
Output power factor (L1, L2, L3), Units 0.00
Bypass phase voltage (L1, L2, L3), Unit 0.1V
Bypass frequency (L1, L2, L3), Units 0.1Hz
Bypass power factor (L1, L2, L3), Units (NA)
Apparent power, Units 0.1kVA
Actual power, Units 0.1kW
Percentage of the UPS rating load, Units 1%