Press the key to view the temperature.
Press and hold the and keys for three second to change the temperature display
between ºC and ºF.
Press the key to turn the light on or off, if your unit has an internal light.
NOTE: When you use the unit for the first time or restart the unit after it has been shut off for a long
time, there could be a few degrees variance between the temperature you select and the one
indicated on the LED readout. This is normal and is due to the length of the activation time.
There should not be a problem once the unit has been running for a few hours.
Setting Parameters:
Several temperature parameter settings can be adjusted from the defaults, if you choose to do so.
To adjust these parameters:
1. Press and hold the SET key for 3 second.
2. When the panel displays St, press the LIGHT key, and the panel will display Po.
3. Press the SET key, and 00 will display.
4. Enter the administrator password (55).
5. Press the SET key, and the panel will display Po.
6. Press the and keys to select the appropriate parameter (do2, A5, A6, etc.).
7. After selecting a parameter, press the SET key to set its value. Use the and keys to adjust
the value, the press the SET key to return to the menu.
8. Press the key, or press no key for 30 seconds, to exit. The temperature set-point will be
saved automatically.
Parameter Table:
Temperature Range: 2°C to 8°C (preset at 4°C)
High Temperature Alarm: Preset at 8°C
Low Temperature Alarm: Preset at 2°C
Door Open Alarm: Set at 60 seconds
Temperature Range: -30°C to -10° C (preset at -25°C)
High Temperature Alarm: Preset at -15°C
Low Temperature Alarm: Preset at -35°C
Door Open Alarm: Set at 60 seconds