Page 16
FAULT TITLE PROBLEM CORRECTIVE ACTION
Back Phase
Loss
Back Phase
Rev
Back Phase
Unbalance
Front Over
Voltage
Front Phase
Loss
Front Phase
Reversal
Front Phase
Unbalance
Front Under
Voltage
Not all three of the
phases on that load
side are present
A voltage unbalanced
between the three load
phases exceeds the
unbalanced setpoint
Average phase-phase
voltage exceeds the
maximum percentage
Not all three of the
phases on the line
side are present
A voltage unbalance
between the three line
phases exceeds the
unbalance setpoint
Average phase-
phase voltage is
below the minimum
percentage
Loads 1, 2, or 3 are
not in sequence
(not 120 phase shifted)
Loads 1, 2, or 3 are
not in sequence
(not 120 phase shifted)
Call factory at: 1-800-KWIKOOL (800-594-5665)
Call factory at: 1-800-KWIKOOL (800-594-5665)
Call factory at: 1-800-KWIKOOL (800-594-5665)
1. Check system for over-voltage cause
2. Increase the percent over-voltage setting if necessary
3. Increase the fault interrogation time if necessary
1. Turn OFF all power
2. Swap any 2 phases on the load side of the Monitor
only (example: swap load 1 and load 2)
3. Re-apply power
1. Press the READ button to observe the present load
voltages. Check system for unbalanced cause
2. Increase the fault interrogation time if necessary
3. Increase the percent unbalance setting if necessary
1. Check system for under-voltage cause
2. Increase the percent under-voltage setting if
necessary
3. Increase the fault interrogation time if necessary
(example:
2. Repair the missing phase
1. Press and hold the READ button on the phase
monitor or use an AC voltmeter to carefully measure
all three phase-phase line voltages
Line 1 Line 2,
Line 2 Line 3, Line 3 Line 1)
XIII / Phase Monitor - Fault Conditions