For PDU3EVSR6G60. Also, The document are for others Tripp Lite models: PDU3EVSR6G60A, PDU3EVSR6L1530, PDU3EVSR6L2120, PDU3EVSR6L2130, PDU3EVN6G60B, PDU3EVN3L2130, PDU3EVN10L2130, PDU3EVN3L2120, PDU3EVN6L2120, PDU3EVN10L2120, PDU3EVN6L2130, PDU3EVSR6H50A, PDU3EVN6G30B, PDU3EVN10G30B, PDU3EVN3G60B, PDU3EVN10G60B, PDU3EVN3H50B, PDU3EVN6H50B, PDU3EVN6H50BA, PDU3EVN10H50B, PDU3EVN3L1520, PDU3EVN6L1520, PDU3EVN10L1520, PDU3EVN3L1530B, PDU3EVN6L1530B, PDU3EVN10L1530B, PDU3EVN3L2130B, PDU3EVN6L2130B, PDU3EVN10L2130B, PDU3EVN2, PDU3EVN6G60C, PDU3EVSR6H50, PDU3EVSR10H50, PDU3EVSR10L1530, PDU3EVSR10L2130, PDU3EVS6H50, PDU3EVS6L2130, PDU3EVS6L2120, PDU3EVSR6L1520, PDU3XEVN6G20, PDU3XEVSR6G20, PDU3XEVSR6G30A, PDU3XEVSR6G30B, PDU3XEVSR6G32A, PDU3XEVSR6G32B, PDU3XEVSR6G60A, PDU3XEVSR6G60B, PDU3XEVSR6G63A, PDU3XEVSR6G63B, PDU3XEVSR6L230B, PDU3XEVSR6L2230, PDU3XEVSRHWA, PDU3XEVSRHWB

PDF File Manual, 18 pages, Read Online | Download pdf file

PDU3EVSR6G60 photo
Loading ...
Loading ...
Loading ...
A B
Remove Access Plate Screws
Ground Terminal
X
Y
Z
N
2-2B
C
9
Installation
Channel the wire through the conduit and insert into the terminal block at locations A, Y, Z,
and N. Secure wires then tighten the screws using a slotted screwdriver and apply a torque of
2.3 N·m (20 in·lb) to each screw. Secure the ground wire to the ground stud and tighten nut.
Connect the conduit to the disconnect device and secure the connector.
21-02-090 93-349E-EN.indd 921-02-090 93-349E-EN.indd 9 2/18/2021 8:53:05 AM2/18/2021 8:53:05 AM