Tripp Lite PDUBHV20 3.2-3.8kW Single-Phase Hot-Swap PDU, 200-240V 16A 6-C13, 2-C19 2-C20, 200-240V Input, 6 ft. 1.83 m Cords 2U Rack-Mount

Owner's Manual - Page 2

For PDUBHV20. Also, The document are for others Tripp Lite models: PDUB15, PDUB20, PDUB30, PDUBHV10

PDF File Manual, 28 pages, Read Online | Download pdf file

PDUBHV20 photo
Loading ...
Mount in top or
bottom holes.
2
Important Safety Warnings
SAVE THESE INSTRUCTIONS
This manual contains important instructions and warnings that should be followed during the installation and operation of this product.
Install the PDU indoors, away from excess moisture or heat, direct sunlight, dust or conductive contaminants. Do not install the PDU near magnetic storage
media, as this may cause data corruption.
Only operate the PDU at indoor temperatures between 32° F and 104° F (0 °C and 40° C). For best results, maintain indoor temperatures between 62° F
and 84° F (17° C and 29° C). For proper ventilation, leave adequate space around all sides of the PDU.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support
equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic
mixture with air, oxygen or nitrous oxide.
Do not connect the PDU to an ungrounded outlet or to adapters that eliminate the connection to ground. The ground connections are provided for your
safety. If the provided plug does not fit your outlet, have a compatible grounded outlet installed by a qualified electrician.
The PDU must be installed near the wall outlet and all plugs must be readily accessible for disconnection.
The PDU must be connected to a wall outlet that is protected by an overcurrent device with the rating shown in the table below:
Model Overcurrent Rating of Protection Device Model Overcurrent Rating of Protection Device
PDUB15 20A PDUBHV10 20A (
c
TUV
us
) or 16A (CE)
PDUB20 20A PDUBHV20 20A (
c
TUV
us
) or 16A (CE)
PDUB30 30A
Caution! Risk of electrical shock! The PDU is supplied by more than one power source. All power sources must be disconnected to de-energize the unit
before servicing.
Do not open the PDU for any reason. There are no user-serviceable parts inside.
CAUTION Only those who are properly trained or qualified to use this device should do so. Anyone who is not trained or qualified should not use this
device unless it is under the supervision of someone who is properly trained or qualified to do so.
Children must be supervised to ensure that they do not use the device as a toy.
Never use the device if the cord and plug are damaged; if it is not working properly, or if it has been dropped or damaged, take it to an authorized service
center for inspection and repair.
If the power cord is damaged, it must be replaced by the manufacturer, its authorized service agent, or by qualified personnel in order to avoid a danger.
Mounting
Mounting (2-Post or 4-Post Racks)
Mount the equipment in either a 2-post or 4-post open frame rack or rack enclosure. The user must determine the fitness of hardware
and procedures before mounting. The procedures described in this manual are for common rack and rack enclosure types and may not be
appropriate for all applications.
Note: Mounting procedures are the same for both 2-post and 4-post rack installation.
Step 1. Attach the mounting ears to the mounting holes of the PDU using the screws provided.
The ears should face forward.
Note: The top or bottom mounting holes of the PDU can be used.
Step 2. Attach the PDU to the rack with user-provided screws, nuts and washers. Insert the
screws through the mounting ears and into the rack rails.
Mounting in the Same Rack Space as a UPS System (4-Post Racks)
The Hot-Swap PDU can be mounted in the same rack space as a UPS system when the
UPS system is mounted using Tripp Lite’s 4POSTRAILKIT. (4POSTRAILKIT is included with
most Tripp Lite UPS systems and is also sold separately. Refer to the UPS system manual or
4POSTRAILKIT manual for UPS system mounting instructions. The procedure for mounting
the rear of the 4POSTRAILKIT mounting shelves to the rack will differ slightly, as shown in this
section.)
Step 1. Attach the mounting ears to the lower mounting holes of the unit using the screws
provided. The ears should face forward.
Step 1
Step 1