5. Installation
5.6 Connexions de plusieurs modules de batteries
DANGER!
S'assurerquelapolaritédelaconnexionensériedel'ensembledebatteriesestcorrecte.NEPAScombiner
desbatteriesdediérentescapacitésdediérentesmarquesoudesbatteriesvieillesetneuves.
AVERTISSEMENT!
S'ASSURER QUE LA POLARITÉ DES CONNEXIONS D'EXTRÉMITÉ DES ENSEMBLES VERS LE DISJONCTEUR DES
BATTERIESETDUDISJONCTEURDESBATTERIESVERSLESBORNESDEL'ONDULEURESTCORRECTE,C.-À-D.(+)
À(+)/(-)À(-)/(N)À(N).DÉCONNECTERUNOUPLUSIEURSLIENSDESÉLÉMENTSDEBATTERIESDANSCHAQUE
NIVEAU. NE PAS RECONNECTER CES LIENS ET NE PAS FERMER LE DISJONCTEUR DES BATTERIES À MOINS QUE
TOUTES LES CONNEXIONS AIENT ÉTÉ CORRECTEMENT VÉRIFIÉES ET APPROUVÉES.
onduleur armoire de batteries
Figure 6-46 : Connexion de BP240V65L et BP240V65L-NIB pour un onduleur de 10 kVA, 15 kVA et 20 kVA