SSaaffeettyy IInnssttrruuccttiioonnss
IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and maintenance
of the UPS. Please read all instructions before operating the equipment and save this manual for
future reference.
This UPS contains its own energy source (batteries).
The DC mains power must be turned off before connecting or disconnecting wires to the
terminals.
Use RED wire for (+) positive and BLACK for (-) negative wire connections.
Make sure the wires do not touch to chassis during their connection.
Always connect the DC mains input and load output wires first, then the UPS battery terminals
labeled (BAT +/-), and finally to the EBM.
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 50°C (122°F). Do not operate near water or excessive humidity (95% max).
To comply with international standards and wiring regulations, the total equipment connected to
the output of this UPS must not have an earth leakage current greater than 1.5 milliamperes.
To guarantee sufficient convection cooling, please keep a clearance of 50mm above, 180mm
below, and 10mm lateral distance of between devices.
Note that the enclosure of the device can become very hot depending on the ambient
temperature and load of the power supply. Risk of burns!
Do not introduce any objects into the unit.
The UPS and EBM unit should be installed in minimum IP54 rated enclosure.
The units must be installed in a cabinet or room (condensation free environment and indoor
location) that is relatively free of conductive contaminants.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the
UPS.