2. Presentation
Description Available settings Default settings
In/Out settings
Load segments -
Auto shutdown
delay
[Disable] [0s] [1 s] [2 s]…[65354 s]
During a power outage,
authorizes UPS to turn off power to
equipment connected to Group 1
and/or Group 2 outlets.
This feature allows the shedding of
non-critical loads in order to conserve
battery power for critical loads
connected to the Primary group.
Group 1: Disable
Group 2: Disable
Overload
prealarm
[10 %] [15 %] [20 %] ... [100 %] [105 %]
Sets critical percentage of load where
alarm overload alarm occurs.
[105 %]
ON/OFF settings
Cold start [Disable] [Enable]
Authorizes the product to start on
battery power.
Enable
Forced reboot [Disable] [Enable]
If mains recover during a shutdown
sequence:
If set to Enable, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disable, shutdown sequence
will not complete and restart will
occur immediately.
Enable
Auto restart [Disable] [Enable]
Authorizes the product to restart
automatically when mains recovers
after a complete battery discharge.
Enable
Energy saving [Disable] [Enable]
If Enable, UPS will shutdown after
5 min. of back-up time, if no load is
detected on the output.
Disable
Sleep mode [Disable] [Enable]
If disable, LCD and communication
will turn OFF immediately after UPS
is OFF.
If enable, LCD and communication
stays ON 1h30 min after UPS is OFF.
Disable
Remote command [Disable] [Enable]
If enable, shutdown or restart
commands from software are
authorised.
Enable
Battery settings
Automatic battery
test
[No test] [Every day] [Every week]
[Every month]
Available only if battery charge mode
is set to constant charge.
Every week
(in constant charge)
otherwise following ABM
Low battery
warning
[1 %] [2 %] ... [100 %]
The alarm triggers when the set
percentage of battery capacity is
reached during a back-up time.
20 %
Restart battery
level
[1 %] [2 %] ... [100 %]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
0 %
Battery charge
mode
[ABM cycling] [Constant charge] ABM cycling
Deep discharge
protection
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Yes