Fire or E×plosion Hazard
Read instruction manual before installing,
using or servicing water heater.
Improper use may result in fire or
explosion.
Maintain required clearances to
combustibles.
Minimum clearances between the water heater and combustible
construction are 0 inch at the sides and rear, 4 inches (102 mm)
at the front, and 6 inches (153 mm) from the vent pipe, see Figure
8. Clearance from the top of the jacket is 12 inches (305 mm)
on most models. Note that a lesser dimension may be allowed
on some models, refer to the label attached adjacent to the gas
control valve on the water heater.
TOP VIEW TOP VIEW
OF CLOSET OF CLOSET
WITHOUT DOOR WITH DOOR
0" MIN.
4" MIN.
(104 mm}
_12" MAX. (30 cm)
VENTIA_R TION
VT_:_ 12" MAX.
(3ocm}
FRONT VIEW
OF DOOR
FIGURE 9.
If this water heater will be used in beauty shops, barber shops,
cleaning establishments, or self-service laundries with dry
cleaning equipment, it is imperative that the water heater or
water heaters be installed so that combustion and ventilation
air be taken directly from outdoors (direct vent).
Propellants of aerosol sprays and volatile compounds, (cleaners,
chlorine based chemicals, refrigerants, etc.) in addition to being highly
flammable in many cases, will also change to corrosive hydrochloric
acid when exposed to the combustion products of the water heater.
The results can be hazardous, and also cause product failure.
Insulation Blankets
Insulation blankets available to the general public for external use
on gas water heaters are not necessary with Kenmore products.
The purpose of an insulation blanket is to reduce the standby
heat loss encountered with storage tank heaters. Your Kenmore
water heater meets or exceeds the National Appliance Energy
Conservation Act standards with respect to insulation and standby
loss requirements, making an insulation blanket unnecessary.
FIGURE 8.
Breathing Hazard - Carbon Monoxide Gas
i
Install water heater in accordance
with the instruction manual and
NFPA 54
To avoid injury, combustion and
ventilation air must be taken from
outdoors.
Do not place chemical vapor
emitting products near water
heater.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
A gas water heater cannot operate properly without the correct
amount of air for combustion, see Figure 9. Do not install in a
confined area such as a closet, unless you provide air as shown
in the Locating The New Water Heater section. Never obstruct
the flow of ventilation air. If you have any doubts or questions at
all, call your gas supplier. Failure to provide the proper amount of
combustion air can result in a fire or explosion and cause death,
serious bodily injury, or property damage.
Breathing Hazard - Carbon Monoxide Gas
- Do not obstruct water heater air
intake with insulating blanket
- Gas and carbon monoxide detectors
are available.
o Install water heater in accordance
with the instruction manual.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
10
A WARNING
Should you choose to apply an insulation blanket to this
heater, you should follow these instructions (See Figure 1 for
identification of components mentioned below). Failure to follow
these instructions can restrict the air flow required for proper
combustion, potentially resulting in fire, asphyxiation, serious
personal injury or death.
Do not apply insulation to the top of the water heater, as this
will interfere with safe operation of the draft hood.
Do not cover the outer door, thermostat or temperature &
pressure relief valve.
Do not allow insulation to come within 2" (50.8 mm) of the floor
to prevent blockage of combustion air flow to the burner.
Do not cover the instruction manual. Keep it on the side of
the water heater or nearby for future reference.