24 English
11. FIELD SETTING
CAUTION
When performing field setting or test run without attaching the decoration panel, do not touch the
drain pump. This may cause electric shock.
Check that the outdoor unit has been wired properly.
Make sure the control box covers are closed on the indoor and outdoor units.
Field setting must be made from the remote controller and in accordance with installation conditions.
Setting can be made by changing the “Mode No.”, “FIRST CODE NO.” and “SECOND CODE NO.”.
For setting procedures and instructions, see “Field settings” in the installation manual provided with the
remote controller.
11-1 Setting ceiling height
Select the SECOND CODE NO. that corresponds to the ceiling height in “Table 4”.
(SECOND CODE NO. is factory set to “01”.)
Ta bl e 4
Note:
1. “Mode No.” setting is done in a batch for the group. To make or confirm settings for an individual unit, set
the internal mode number in parentheses.
2. The figure of the ceiling height is for the all round outlet. For the settings for four-direction (part of corner
closed off), three-direction and two-direction outlets, see the installation manual supplied with the sealing
member of air discharge kit sold separately.
11-2 Setting of air direction
See the installation manual supplied with the sealing member of air discharge outlet kit sold separately
technical guide, for ceiling height settings for two and three-direction air discharge.
(The SECOND CODE NO. is factory set to “01” (all round outlet) before shipping.)
11-3 Settings for optional accessories
When installing optional accessories, refer to the installation manual provided with them and make neces-
sary settings.
FCQ - PAVJU
Mode No.
Note) 1
FIRST
CODE NO.
SECOND
CODE NO.
18 · 24 · 30 type
36 · 42 type
Ceiling
height (ft.)
Standard · All
round outlet
8-3/4 10-1/2
13 (23) 0
01
High ceiling 1 8-3/4 - 10 10-1/2 - 12 02
High ceiling 2 10 - 11-1/2 12 - 13-3/4 03
Mode No.
FIELD SET MODE
SECOND CODE NO.
FIRST CODE NO.
Mode
10
Field settings
0
01
4
–––
8
–––
Return Setting
01_EN_3P161684-6K.fm Page 24 Friday, September 16, 2011 10:00 PM