Tripp Lite SMART2600RM2U SmartPro 120V 2200VA 1.92kW Line-Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9

Owner’s Manual - Page 17

For SMART2600RM2U. Also, The document are for others Tripp Lite models: SMART2200RM2U, SMART2200RM2UN, SMART3000RM2U, SMART3000RM2UN, SMART2000RMXL2U, SMART2200RMXL2U, SMART2200RMXLN, SMART3000RMXL2U, SMART3000RMXLN, SM2200RMXL2UP

PDF File Manual, 68 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
17
15A 120V
NEMA 5-15R
20A 120V
NEMA 5-20R
30A 120V
NEMA L5-30R
20A 120V
NEMA L5-20R
Basic Operation
Other UPS Features (Rear Panel)
AC Outlets: All models include NEMA 5-15R and/or NEMA
5-20R outlets. Select models also include NEMA L5-30R and/or NEMA L5-20R
outlets. These outlets provide your connected equipment with AC line power
during normal operation and battery power during blackouts and brownouts. The
UPS protects equipment connected to these outlets against damaging surges
and line noise. If you have a serial or USB connection to your UPS, you can
remotely reboot connected equipment by turning the outlets OFF and ON using
Tripp Lite’s PowerAlert Software. The outlets are divided into one or more load
banks (labelled “LOAD 1,” etc.) which may be remotely switched OFF and ON
without interrupting power to equipment connected to the other outlets. Outlets
labelled “UNSWITCHED” may not be remotely switched off.
Communications Ports (USB or RS-232): These ports connect your UPS to
any workstation or server. Use with Tripp Lite’s PowerAlert Software and included
cables to enable your computer to automatically save open files and shut down
equipment during a blackout. Also use PowerAlert Software to monitor a wide
variety of AC line power and UPS operating conditions. Consult your PowerAlert
Software manual or contact Tripp Lite Customer Support for more information.
See “USB and RS-232 Serial Communications” in the “Optional Installation”
section for installation instructions.
EPO (Emergency Power Off) Port: Your UPS features a EPO port that may be
used to connect the UPS to a contact closure switch to enable emergency
inverter shutdown. See Optional Installation.
Accessory Slot: Remove the small cover panel from this slot to install optional
accessories to remotely monitor and control your UPS. Refer to your accessory’s
manual for installation instructions. Contact Tripp Lite Customer Support at
www.tripplite.com/support for more information, including a list of available
SNMP, network management and connectivity products.
Note: Select models include a preinstalled network management card. For these models,
refer to the management card accessory user manual included with your UPS for
connection, configuration and complete operating instructions.
External Battery Connector (optional on select models): Use to connect
Tripp Lite external battery packs for additional runtime. Refer to instructions
available with the battery pack for complete connection information and safety
warnings. Visit http://www.tripplite.com/products/battery-finder/ to locate the
supported battery type(s) for your UPS.
21-07-111-933088-Book.indb 1721-07-111-933088-Book.indb 17 7/28/2021 4:49:39 PM7/28/2021 4:49:39 PM
Loading ...
Loading ...
Loading ...