Tripp Lite SRCOOL7KRM AC Unit for Server Racks - Rack Mount, 7,000 BTU 2.0 kW, 120V, 8U

Owner's Manual - Page 9

For SRCOOL7KRM.

PDF File Manual, 32 pages, Read Online | Download pdf file

Loading ...
Loading ...
Loading ...
9
Additional Display Codes
Troubleshooting
Review the possible solutions below. If the problem persists, please visit www.tripplite.com/support for service.
Problem Possible Cause Possible Solution
The unit does not function. The unit is turned off. Turn the unit on. (See “Operation” section.)
The unit is not plugged in. Plug the unit into a suitable outlet.
Main power is off. Check fuses or circuit breaker.
Cooling performance is unsatisfactory. The air exhaust or intake is blocked. Confirm that all ducts and intakes are clear of obstructions.
The temperature setting is too high. Adjust the temperature setting.
The fan speed setting is too low. Adjust the fan setting.
The air filter is dirty. Clean the air filter.
The wattage of the rack enclosure, the size of
the room or the ambient temperature exceeds
the cooling capacity of a single unit.
Install additional units or contact Tripp Lite for additional cooling solutions suitable for
your application.
The unit leaks water. The drainage plug is not installed. Insert the drainage plug in the drainage outlet. (See “Installation” section.)
The unit has ice or frost buildup. The unit is operating in an environment that is
too cool or has excess humidity.
OPTION 1: Turn off the unit, and let the unit defrost. Once defrosted, ensure the unit
is operating with the fan speed set on HIGH.
OPTION 2: Turn off the unit, and let the unit defrost. Once defrosted, operate the unit
in DEHUMIDIFY MODE, or increase the desired temperature setpoint.
Display Code Description
df Unit is in Defrost Mode
E1 Indoor Temperature Sensor Error
E2 Internal Temperature Sensor Error
E4 Water Full Error
Defrost Mode
If the “df” code appears, it means the unit detected an icing problem and has started a defrost
cycle. The compressor will stop and the upper motor will continue to run at high speed for
3.5 minutes.
If the icing problem clears up, the unit will return to normal operation. If the code returns,
check the humidity and temperature of the operating environment. An environment that is too
cool or has excessive humidity can cause icing problems. If the operating environment is normal
and you are still getting the “df” code, contact Tripp Lite for further instructions.
Error Codes
The Tripp Lite SRCOOL7KRM has the ability to continually monitor itself. Should an error occur,
the display will show one of 3 error codes to the left:
Code E4 can be cleared by emptying the water tank. Consult the Alarm entry in the Operation
section for details.
For Codes E1 and E2 follow these steps:
1. Power cycle the unit by unplugging it from the source for 5 minutes.
2. Plug the unit back in.
3. Restart the unit.
If the code remains clear, continue to operate the unit as normal. If the code returns, please
contact Tripp Lite for further instructions.