Eaton Tripp Lite SmartOnline Series User Guide 614-40206—Rev 01 13
Table 3. SmartOnline Transformer I/O Output Voltage
Input voltage SmartOnline transformer output voltage
(from UPS)
208V Switch position 240V Switch position
5–20R 5–20R
200 115 100
208 120 104
220 127 110
230 133 115
240 138 120
250 144 125
6. Close the front cover and secure it with the two phillips-head.
7. Replace the square center cover.
8. Plug the transformer into one of the L6–30 receptacles on the back of the UPS. See
Figure 9 and Figure 10
.
NOTE Refer to the UPS User's Guide for additional installation and system configuration
information.
Figure 9. Rack-mounted Transformer Electrical Connection
Transformer connected
to UPS output
Transformer Electrical Connections
Loading ...
Loading ...
Loading ...