Tripp Lite SVX180KL SmartOnline SVX Series 180kVA Modular, Scalable 3-Phase, On-line Double-Conversion 400/230V 50/60Hz UPS System

Owner's Manual - Page 20

For SVX180KL. Series: SVX Series

PDF File Manual, 148 pages, Read Online | Download pdf file

SVX180KL photo
Loading ...
Loading ...
Loading ...
20
9. Control Panel
9.1 Introduction/Operation
To Turn ON the UPS:
Once all modules are assembled and installation cabling is complete:
1. Switch ON Internal/External Battery Breakers.
2. Switch ON Main Input Breaker (Q1) located on the front of the breaker panel (the LCD panel will display “Bypass Mode”).
3. Press the Power button for 2 seconds; the UPS is now in “Line Mode”.
4. Switch ON Output Breaker (Q3). Parameters can now be viewed, adjusted and programmed via the control panel located on the front of the
UPS system.
To Turn OFF the UPS:
WARNING
The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm all loads
are turned off.
1. Press the Power button for 2 seconds.
2. UPS will transfer to Bypass Mode or Standby mode if bypass is disabled.
Note: UPS will have no output when in Standby Mode.
3. Switch OFF Output Breaker (Q3).
4. Switch OFF Main Input Breaker (Q1).
5. Wait 1 minute and then shut off battery breakers.
Note: To be fully de-energized, UPS must be disconnected from AC input.
The Control Panel is the user control and interface for all measured parameters, UPS and battery status and alarms and is divided into three
areas:
1
LCD Display – Graphic display and all measured parameters
2
LED Indicators – refer to table 9.1
3
Control Keys – refer to table 9.2
1
3
2
Figure 9.1
LED Color Status Definition
INPUT Green On Input source is normal
Flashing Input source is abnormal
Off No input source
BYPASS Amber On Load is on bypass
Flashing Input source is abnormal
Off Bypass is not functioning
INVERTER Green On Load is on inverter
Off Inverter is not functioning
BATTERY Red On Load is on battery
Flashing Low battery
Off Normal operation, battery is charging
ALARM Red On UPS fault
Flashing UPS alarm
Off No alarms
Table 9.1