58
4. Operation
Chg. cur. limiting coef. (C): The charging current limit is a multiple of the battery capacity. The value range is 0.05 to
0.25. The default value is 0.15. Consult the specic battery cabinet owner’s manual for the recommended Coecient
(Coef.) based on the S3M UPS model and battery cabinet model.
Celloatvoltage(V/Cell): The oat voltage value range is 2.20 to 2.29 V/cell. The default value is 2.27 V/cell.
Cell boost voltage (V/Cell): The battery equalized voltage value range is 2.30 to 2.40 V/cell. The default value is 2.35 V/
cell.
Aver Charging Duration (min): Boost charge time limit. The value range is 1 to 999 minutes. The default value is 240.
Consult the specic battery cabinet owner’s manual for the recommended Aver Charging Duration (min) based on the
S3M UPS model and battery cabinet model.
Figure 4-31B: Battery Settings
EOD Battery Volt (V/Cell): End of discharge voltage. The value range is 1.60 to 1.90. The default value is 1.67.
FloatTempCompenCoef.(V/Cell/°C): Modify the voltage of compensation after enabling the switch. The value range
is 0.001 to 0.007/cell. The default value is 0.003.
Boost Charge Setting: Boost charge setting is disable or enable. The default is enable.
No Battery Warning: When set to Disable, the buzzer will not sound. Set to Enable for audible battery warnings. The
default is enable.