Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01 33
CChhaapptteerr 55 UUPPSS MMaaiinntteennaannccee
55..11 EEqquuiippmmeenntt CCaarree
For the best preventive maintenance, keep the area around the equipment clean and dust free. If the
atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the
equipment at an ambient temperature of 25 °C (77 °F).
If the UPS requires any type of transportation, verify that the UPS is disconnected and turned off. The batteries
are rated for a 3-5 year service life. The length of service life varies, depending on the frequency of usage and
ambient temperature (life divided by 2 each 10 °C above 25 °C).
Batteries used beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 4 years to keep units running at peak efficiency. Batteries runtime will be reduced at low
temperature (below 10 °C).
55..22 SSttoorriinngg tthhee EEqquuiippmmeenntt
If you store the equipment for a long period, recharge the battery every 6 months by connecting the UPS to
utility power. The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton recommends
that the batteries charge for 24 hours after long-term storage. Check the battery recharge date on the shipping
carton label. If the date has passed and the batteries were never recharged, do not use them. Contact your
service representative.
55..33 WWhheenn ttoo RReeppllaaccee BBaatttteerriieess
Tripp Lite by Eaton UPS batteries have an expected life span of 3-5 years. You should take proactive steps to
ensure you replace your batteries for optimal operation and reliability.
Contact your service representative to order new batteries.
55..44 RReeppllaacciinngg bbaatttteerriieess
!
IMPORTANT
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
Batteries can be replaced easily without turning off the UPS or disconnecting the load. If you prefer to remove
input power to change the batteries, see "UPS Shutdown".
Consider all warnings, cautions, and notes before replacing batteries.
Servicing should be performed by qualified service personnel knowledgeable of batteries and required
precautions. Keep unauthorized personnel away from batteries.
Batteries can present a risk of electrical shock or burn from high short circuit current. Observe the
following precautions:
1. Remove watches, rings, or other metal objects,
2. Use tools with insulated handles,
3. Do not lay tools or metal parts on top of batteries,
4. Wear rubber gloves and boots.
When replacing batteries, replace with the same type and number of batteries or battery packs. Contact
your service representative to order new batteries.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.