28
9. Control Panel
System
Data User Adjustable / Section Reference
Nominal Power (kW) -
Nominal AC Voltage (V) Yes / 9.3.6.2 System
Nominal Frequency (Hz) Yes / 9.3.6.2 System
Number of Modules Yes / 7.2.1 Installing a Power Module
Number of Modules for Redundancy Yes / 9.3.6.2 System
System Installed Date Yes / 9.3.6.1 General
System Last Maintain Date Yes / 9.3.6.1 General
ECO Mode Yes / 9.3.6.2 System
Converter Mode Yes / 9.3.6.2 System
Battery Mode Shutdown Delay Yes / 9.3.6.2 System
Auto Restart Yes / 9.3.6.2 System
Power by Bypass Yes / 8.1 Transfer to Bypass via STS Module Connector from UPS
Mode & 8.2 Transfer to Bypass via Control Panel
Cold Start Yes / 7.3 Cold Start & 9.3.6.2 System
System Language Yes / 9.3.6.1 General
Change Password Yes / 9.3.6.1
Battery
Data User Adjustable / Section Reference
Nominal Battery Voltage (V) No
Battery Capacity in Ah Yes / 9.3.6.3 Battery
Maximum Charging Current (A) Yes / 9.3.6.3 Battery
Battery Low Voltage (V) Yes / 9.3.6.3 Battery
Battery Low Capacity (%) Yes / 9.3.6.3 Battery
Battery Shutdown Voltage (V) Yes / 9.3.6.3 Battery
Periodic Battery Test Yes / 9.3.6.3 Battery
Battery Installed Date Yes / 9.3.6.1 General
Battery Last Maintain Date Yes / 9.3.6.1 General
Temperature Compensation Yes / 9.3.6.3 Battery
9.3.8 Events Screen
When an event occurs, a flashing “Warning” text alerting the event will automatically appear in the center of the “Home” screen.
The “Events” screens may be referenced to view both current events and historical events.
Use “Down/Right” key to select “Events” option. Press “Enter” key to enter “Events” sub-menu.
HOME
MENU
EVENTS
Current Events
History Events
Reset All Events
9.3.8.1 Current Events
When an event occurs, the Power Module ID and a text summary will be displayed in the “Current Events” screen. Four events are visible on
screen at any one time; if there are more than four events, use the “Down/Right” and “Up/Left” keys to scroll through the list. Up to 500 events
may be viewed via the “Current Events” screen.
Loading ...
Loading ...
Loading ...