LG Electronics LUU488HV LG Air Conditioner Cooling Area,

User Manual - Page 53

For LUU488HV.

PDF File Manual, 82 pages, Read Online | Download pdf file

LUU488HV photo
Loading ...
Loading ...
Loading ...
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
PRODUCT DATA | 53
Product Data
Table 27: Cooling Capacity Table for LUU248HV + LVN240HV4.
Cooling Capacity Table for LV240HV4 (LUU248HV + LVN240HV4)
Out-
door Air
Temp.
(°F DB)
Indoor Air Temp. °F DB / °F WB
68 / 57 72 / 61 77 / 64 80 / 67 86 / 72 90 / 75
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-4 23.60 17.36 1.14 25.06 18.34 1.18 26.53 17.75 1.22 27.58 18.13 1.23 29.46 18.28 1.26 30.92 18.63 1.28
0 23.58 17.46 1.15 25.05 18.44 1.19 26.51 17.86 1.23 27.57 18.23 1.25 29.44 18.39 1.27 30.91 18.74 1.30
5 23.56 17.61 1.17 25.03 18.60 1.21 26.49 18.01 1.25 27.55 18.39 1.27 29.42 18.55 1.29 30.88 18.90 1.32
10 23.55 17.75 1.18 25.01 18.75 1.23 26.47 18.16 1.27 27.53 18.54 1.29 29.39 18.70 1.31 30.86 19.05 1.34
15 23.53 17.89 1.20 24.99 18.90 1.25 26.45 18.30 1.29 27.50 18.69 1.31 29.37 18.84 1.33 30.83 19.20 1.36
20 23.51 18.03 1.22 24.97 19.05 1.26 26.43 18.44 1.31 27.48 18.83 1.32 29.35 18.99 1.35 30.81 19.35 1.38
25 23.49 18.17 1.24 24.95 19.20 1.28 26.41 18.59 1.33 27.46 18.98 1.34 29.33 19.14 1.37 30.79 19.50 1.40
30 23.47 18.31 1.25 24.93 19.34 1.30 26.39 18.73 1.35 27.44 19.12 1.36 29.30 19.28 1.39 30.76 19.65 1.42
35 23.46 18.45 1.27 24.91 19.49 1.32 26.37 18.87 1.37 27.42 19.27 1.38 29.28 19.43 1.41 30.74 19.80 1.43
40 23.44 18.59 1.29 24.89 19.64 1.33 26.35 19.01 1.38 27.40 19.41 1.40 29.26 19.58 1.43 30.72 19.95 1.45
45 23.42 18.73 1.31 24.87 19.78 1.35 26.33 19.15 1.40 27.38 19.56 1.42 29.24 19.72 1.44 30.69 20.10 1.47
50 23.40 18.87 1.32 24.85 19.93 1.37 26.31 19.30 1.42 27.36 19.70 1.44 29.21 19.87 1.46 30.67 20.24 1.49
55 23.38 19.00 1.34 24.84 20.07 1.39 26.29 19.44 1.44 27.34 19.85 1.46 29.19 20.01 1.48 30.64 20.39 1.51
60 23.37 19.14 1.36 24.82 20.22 1.41 26.27 19.58 1.46 27.32 19.99 1.47 29.17 20.16 1.50 30.62 20.54 1.53
65 23.35 19.28 1.37 24.80 20.37 1.42 26.25 19.72 1.48 27.29 20.13 1.49 29.15 20.30 1.52 30.60 20.69 1.55
70 23.33 19.42 1.39 24.78 20.51 1.44 26.23 19.86 1.49 27.27 20.28 1.51 29.13 20.45 1.54 30.57 20.84 1.57
75 22.77 19.10 1.47 24.21 20.20 1.52 25.66 19.58 1.58 26.70 20.01 1.59 28.55 20.20 1.62 29.99 20.60 1.66
80 22.21 18.77 1.54 23.65 19.88 1.60 25.09 19.30 1.66 26.13 19.73 1.68 27.97 19.95 1.71 29.42 20.36 1.74
85 21.65 18.43 1.62 23.09 19.55 1.68 24.53 18.99 1.74 25.57 19.44 1.76 27.40 19.68 1.79 28.84 20.10 1.83
90 21.09 18.08 1.69 22.53 19.21 1.75 23.96 18.69 1.82 25.00 19.14 1.84 26.83 19.40 1.87 28.27 19.84 1.91
95 20.49 17.89 1.77 21.92 19.03 1.83 23.35 18.55 1.90 24.00 18.72 1.92 26.20 19.30 1.96 27.63 19.75 2.00
100 19.99 17.41 1.84 21.42 18.55 1.91 22.85 18.10 1.98 23.69 18.43 2.00 25.70 18.88 2.04 27.13 19.35 2.08
105 19.49 16.93 1.92 20.92 18.07 1.99 22.35 17.66 2.06 23.38 18.14 2.08 25.20 18.47 2.12 26.63 18.94 2.16
110 18.99 16.35 1.99 20.42 17.49 2.06 21.85 17.12 2.14 22.88 17.60 2.16 24.70 17.94 2.21 26.13 18.42 2.25
115 18.49 15.86 2.07 19.92 17.00 2.14 21.35 16.66 2.22 22.38 17.15 2.25 24.20 17.51 2.29 25.63 18.00 2.33
118 18.19 15.75 2.11 19.62 16.89 2.19 21.05 16.58 2.27 22.08 17.07 2.30 23.90 17.46 2.34 25.33 17.96 2.39
122 18.10 15.71 2.17 19.52 16.86 2.25 20.95 16.55 2.33 21.98 17.05 2.36 23.81 17.44 2.40 25.23 17.94 2.45
PERFORMANCE DATA
Cooling Capacity Tables
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity
(kBtu/h)
SHC: Sensible Capacity (kBtu/h) PI: Power Input (kW) (includes compressor, indoor fan
motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Cooling operating range with the Low Ambient Baffle Kit (sold separately) is -4°F to
+122°F.
3. Grey shading indicates reference data. When operating the unit at this temperature,
these values can be different by discontinuous operation.
4. Direct interpolation is permissible.
Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).
Loading ...
Loading ...
Loading ...