KBU55ASD KingsBottle 24 Inch Stainless Steel Beverage Center

User Manual - Page 8

For KBU55ASD.

PDF File Manual, 16 pages, Read Online | Download pdf file

KBU55ASD photo
Loading ...
Loading ...
Loading ...
ADJUST TEMPERATURE
1. Press the “SET / MUTE” button for more than 3
sec. ,the display shows the parameter code “ST/
VALUE/PS/0” , 0 is the PASSWORD.
2. Release the button when it shows ST/0.
3. Use the “UP” and “DOWN” buttons to adjust the
temperature.
4. Press SET / MUTE button, or if no button is
pressed for 5 seconds, the change of setting is
saved and the DISPLAY will show the actual
temperature.
MODIFYING THE PARAMETERS
!
The operating parameters are modifiable using the keypad.
Access to the parameters is protected by password (default = 22) to prevent accidental or unauthorised modifications.
!
Accessing the Parameters:
1. Press the “SET / MUTE” button for more than 5 sec. , the display shows the parameter code “PS/0
2. Press the “SET / MUTE” button to access the password setting; the display shows the parameter starting value “0”; use the “UP” and
“DOWN” buttons to scroll the numbers until displaying “22” (default password);
3. Press the “SET / MUTE” button to confirm the password; the display shows the parameter code “PS” (password);
4. Repeat the following procedure for any parameter that needs to be modified :
4.1. Use the “UP” and “DOWN” buttons to scroll the parameters codes and choose the parameter that needs to be modified.
4.2. The Category of the parameter chose, determines the Initial letter of the code and the Icon that is turned on :!
4.3. Press “SET / MUTE” to display the value associated with the parameter code; increase or decrease the value using the “UP” or
”DOWN” button respectively;
4.4. Press “SET / MUTE” to temporarily save the new value and display the parameter code again;
!
WARNINGS:
If no button is pressed for 60 sec. or if the power is disconnected from the instrument before saving the settings : all of the changes
made to the parameters and temporarily saved in the RAM, will be cancelled and the previous settings will be restored.
5. Press “SET / MUTE” button for more than 3 sec. to permanently save the parameters and exit the parameter setting procedure.
!
SETTING THE DEFAULT VALUES
!
To reset the default parameters:
1. disconnect power from the instrument;
2. reconnect power while holding both the “SET / MUTE” and “DOWN / LIGHT” buttons;
3. the display will show the message “CF”;
4. after a few seconds the instrument starts operating with the default configuration. Any different parameter settings will need to be
updated.
!
WARNINGS:
running this procedure overwrites any custom parameter settings.
! ! ON
Compressor
activation
request
!!OFF
OPERATION
COMPRESSOR BEVERAGE COOLER
www.kingsbottle.com" 8
Loading ...
Loading ...
Loading ...