Frigate HRV(ERV) 120 S
CONDENSATE DRAINAGE
Fig. 4. Wall unit mounting
The Vents Frigate HRV 120 S unit is equipped with a condensate drain hose for condensate
drainage (g. 5). Connect the drain hose (1), U-trap (3) and drain system (5) with metal, plastic or
rubber pipes (2 and 4). The pipes must be sloped down at least by 3°. Before starting operation of
the unit ll the system with water and check that U-trap is always lled with water. Make sure that
the water drainage is correct, otherwise some condensate may be accumulated inside the unit and
provoke subsequent equipment damage and water ingress to the room. The condensate drainage
system is designed for operation at the ambient temperature above 32 ºF (0 °С). If the ambient
temperature is below 32 ºF (0 °С), insulate the drain system and provide air heating.
min 3°
1
3
5
2
4
g. 5. Condensate drainage
This installation example is applicable
only for Vents Frigate ERV 120 S