Controller must be handled by a qualified technician.
Relay outputs
SSR outputs
Connessioni
depending on the model
Model Relay P. Supply Probes for wires from 12 A
EN 60730-1 UL 873
model
IRxxxxxx0xx screw screw screw 0.5 a 2.5 mm²
IRxxxxxx2xx removable removable removable
IRxxxx(E,A)x5xx vertical screw vertical screw vertical screw
IRxxxx(E,A)x1xx faston faston removable
IRxxxx(E,A)x3xx faston faston screw
relay
R2 (*)
R3 (*)
R1,R2
R1
R2,R3
R1 (*)
R4 (*)
250 V~ 250 V~
5(1)A 5 A resistive 1FLA
5 A resistive 1FLA
8 A resistive 2FLA
12 A resistive 5FLA
6 LRA C 300
6 LRA C 300
5(1)A
8 (4)A N.O.
6 (4)A N.C. 12 LRA
2 (2)A N.O./N.C. C300
30 LRA C300
12 (2)A N.O./N.C.
operating operating
100000 300000
100000 300000
100000 300000
100000 300000
(*): Relay not suitable for uorescent loads (neon lights, ...) that use starters (ballasts) with phase-shift
the installer has to provide the correct dimensioning of the power supply and cable connection between the
cycles cycles
capacitors. Fluorescent lamps with electronic control devices or without phase-shift capacitors can be used,
instruments and the loads. Depending on the model, the maximum current in the common terminals 1, 3 or 5 is
Type of connection
Cross-section Max. current
IRxxxx(E,A)
IRxxxx(E,A)
IRxxxx(E,A)
IRxxxx(E,A)
IRxxxx(O,L,H)
IRxxxx(O,L,H)
(N,R,C,B,A,M,L,T)xxx
(N,R,C,B,A,M,L,T)xxx
(P,Q,S,U,V,X,Y,Z)xxx
(N,R,C,B,A,M,L,T)xxx
(N,R,C,B,A,M,L,T)xxx
(P,Q,S,U,V,X,Y,Z)xxx
within the operating limits specied for each type of relay.
12 A. When using the controller at maximum operating temperature and full load, use cables featuring a
maximum operating temperature of 105 ºC at least.
reinforced
basic
3 mm clearance, 4 mm creepage
1250 V insulation
6 mm clearance, 8 mm creepageinsulation from very low voltage parts
insulation between the relay outputs indipendent
Max output voltage : 12 Vdc, Output resistance: 600 Ω, Max output current: 20 mA
3750 V insulation