Santa Fe 4042660 Mini Ceiling HEPA Air Purifier

User Manual - Page 7

For 4042660.

PDF File Manual, 11 pages, Read Online | Download pdf file

4042660 photo
Loading ...
Loading ...
Loading ...
7
800.533.7533 | Santa-Fe-Products.com Santa Fe Ceiling HEPA Installation & Operation Instructions
INSTALLATION INSTRUCTIONS
To obtain maximum HEPA system performance, the use of aluminum tape and/or nylon strapping is
needed to secure ducting to the duct collars.
Do not locate the return grill lter box near the supply diusers. They should be located 8’ minimum
apart. If ceiling geometry does not allow this specication, locate the return and diusers as far apart as is
practical.
Wiring the Santa Fe Ceiling HEPA
NOTE: All electrical connections must be installed by a qualied electrician. All wiring must conform to the
local electric codes and/or the National Electrical Code.
The Santa Fe Ceiling HEPA uses a 115 volt, 10 amp circuit which is connected to the black and white wires in
the electrical cabinet (see Fig. 3). Additionally, the included grounded power cord may be used in non-plenum
rated space above the drop ceiling provided 115 Volt grounded outlet is available.
WIRING
Figure 3
10-15 Amp 115
Volt Circuit with
Ground from Main
Electrical Service
GROUNDED
PLUG
4036523
SWITCH 1
4035825
BLOWER 1
4028240
BLOWER 2
4028240
WHITE
20AWG
WHITE
14AWG
BLACK
20AWG
BLACK
20AWG
SWITCH 2
4035825
BLACK
18AWG
103-017
BLACK
14AWG
CIRCUIT BREAKER
5 AMP
103-031
GROUNDED
PLUG
4036523
BLOWER
4028240
WHITE
14AWG
BLACK
20AWG
BLACK
14AWG
SWITCH
4035825
WHITE
20AWG
CIRCUIT BREAKER
5 AMP
103-031
Standard: 2 Fan Box Mini: 1 Fan Box
Wiring Schematics
Loading ...
Loading ...
Loading ...