5
Technical Information
Service Manual
Outdoor
Unit
Cross-sectional Area of Power Cable Conductor sq in 0.013 0.013
Recommended Power Cable(Core) N 3 3
Connection Pipe Connection Method - Flare Connection Flare Connection
Not Additional Gas Connection Pipe Length ft 131.2 131.2
Connection Pipe Gas Additional Charge oz/ft. 0.2 0.2
Outer Diameter of Liquid Pipe1(GREE Allocation)
(Metric)
inch 1/4 1/4
Outer Diameter of Liquid Pipe2(GREE Allocation)
(Metric)
inch 1/4 1/4
Outer Diameter of Liquid Pipe3(GREE Allocation)
(Metric)
inch 1/4 1/4
Outer Diameter of Liquid Pipe4(GREE Allocation)
(Metric)
inch 1/4 1/4
Outer Diameter of Liquid Pipe4(GREE Allocation)
(Metric)
inch / 1/4
Outer Diameter of Gas Pipe1(GREE Allocation)
(Metric)
inch 3/8 3/8
Outer Diameter of Gas Pipe2(GREE Allocation)
(Metric)
inch 3/8 3/8
Outer Diameter of Gas Pipe3(GREE Allocation)
(Metric)
inch 3/8 3/8
Outer Diameter of Gas Pipe4(GREE Allocation)
(Metric)
inch 3/8 3/8
Outer Diameter of Gas Pipe4(GREE Allocation)
(Metric)
inch / 3/8
Connection Pipe Max. Height Distance(indoor and
indoor)
ft 49.2 49.2
Connection Pipe Max. Height Distance(indoor and
outdoor and indoor up)
ft 49.2 49.2
Connection Pipe Max. Height Distance(indoor and
outdoor and outdoor up)
ft 49.2 49.2
Max. equivalent connection pipe length(outdoor to
last indoor)
ft 82.0 82.0
Connection Pipe Max. Length Distance(total lenght) ft 246.1 262.5
The above data is subject to change without notice; please refer to the nameplate of the unit.