Royal Sovereign RDHC-110 110 Pint Commercial Dehumidifier

User Manual - Page 11

For RDHC-110.

PDF File Manual, 32 pages, Read Online | Download pdf file

RDHC-110 photo
Loading ...
Loading ...
Loading ...
RDHC-110
11
The humidity can be decreased by increments of 5 %RH during normal mode. Hold this button for 1 second to decrease the humidity.
Note: 1) The default humidity is 50 %RH,with increase and decrease increments as outlined below:
20 %-25 %-30 %-35 %-40 %-45 %-50 %-55 %-60 %-65 %-70 %-75 %-80 %-85 %-90 %
2) Environmental and the unit set humidity will control the status of the units compressor and fan.
If the environmental humidity is >= the machine set humidity +3 %, the compressor and fan will operate.
If the environmental humidity is < the machine set humidity +3 %, the compressor and will will not operate.
Press the continue button for continuous mode or switch to normal dehumidification mode to set the humidity normally
During continuous mode, humidity setting is unavailable. The continuous mode light turns on and the screen will display the current humidity. Press
this button to switch to normal mode where the humidity setting will be available.
OPERATION
When the water tank is full, the water tank LED light will be red and an alarm will sound after 5 seconds. A buzzer sound beeps 15 times and the compressor
and fan will shut off. Empty the water tank and restart. After the water tank is empty, the unit will automatically switch to its previous setting with the
compressor will remain in a 3 minute self-protect stats. The alarm will stop 3 seconds after the water tank is emptied and replaced. The fan and
compressor will start again after 3 minutes.
Note: The compressor will not go into ‘self-protect’ mode, if it is the first time the unit has been used. Press “POWER” to restart the compressor.
The system has auto memory function. If there is sudden power cut during operation, or the power jack slips out, the unit will
return to the previous setting.
DEFROST FUNCTION
1) The compressor and fan will shut off automatically when the environmental temperature goes below 5°C (41 °F) or above 38°C (100.4°F).

compressor will stop and defrosting will begin. The fan will continue operation with the defrost light on. When the pipe temperature reaches 5°C (41°F) or
the defrost function lasts for 15 minutes, the defrost function will stop.
Note: During defrost function the LED light will be off until defrosting is complete.