For wired remote controller
1) Set to COOL or HEAT operation using the remote
controller.
2) PressandholdCancelbuttonfor4secondsorlonger.
Service settings menu is displayed.
3) Select
Test Operation in the service settings menu, and
press Menu/OK button. Basic screen returns and “Test
Operation” is displayed at the bottom.
4) PressOn/Offbuttonwithin10seconds,andthetest
operation starts.
Monitor the operation of the indoor unit for a minimum
of 10 minutes. During test operation, the indoor unit
will continue to cool/heat regardless of the temperature
setpoint and room temperature.
• In the case of above-mentioned procedures 3) and 4)
in reverse order, test operation can start as well.
5) PressandholdCancelbuttonfor4secondsorlongerin
the basic screen.
Service settings menu is displayed.
6) Select
Test Operation in the service settings menu, and
press Menu/OK button. Basic screen returns and normal
operation is conducted.
• Test operation will stop automatically after 15-30
minutes. To stop the operation, press On/Off button.
Basic screen
1)
2)
Cool
Return Cleanthelter
Set to
Cool
68F
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Service Settings
menu screen
3)
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
Press Menu/OK button.
4)
Set temperature
80°F
Cool
Test Operation
Press On/Off button
(within 10 seconds).
5)
Set temperature
80°F
Cool
Test Operation
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
6)
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
Press Menu/OK button.
Basic screen
English 16
Loading ...
Loading ...
Loading ...