Rinnai 12 EHPA Heat Pump OIM
SYSTEM SPECIFICATIONS
EHPA250VM EHPA315VM
Net Weight / Weight Filled 112 kg / 390 kg 132 kg / 445 kg
Sound Level 48 dB
Ambient Temperature Limits
(for heat pump operation - element will
operate beyond these limits)
-1°C to 45°C
Ingress Protection IP24
Storage Cylinder - Hot Outlet and Cold inlet
Connections
ISO 7.1 ¾” RP
Storage Cylinder - PTR Valve Connection ISO 7.1 ½” RP
Pressure & Temperature Relief (PTR) Valve
(Supplied) Setting / Rating
1000 kPa / 10kW
ECV Fitted
Fit PLV if mains
pressure exceeds
680 kPa
Recommended PLV
pressure rating
500 kPa
ECV Not Fitted
Fit PLV if mains
pressure exceeds
800 kPa
Recommended PLV
pressure rating
500 kPa
Rated Input Electric Element
(Factory Wired)
2.4 kW
Rated Input Refrigeration Module
(Factory Wired)
1.0 KW
Total Rated Input (To be wired by installer) 3.4 KW
Maximum Energy Output
(Use to size PTR)
4.29 kW
Power Supply 240 V AC, 50 Hz.
Rated Current 15 A
Refrigerant Type / Mass R290 / 300 g
Refrigerant Compressor Oil Type / Charge Type: ISO VG 32 ESTER / 500 cm³
Refrigerant Circuit Maximum Pressure 3800 kPa
Startup Protection
When the power is rst turned on to the heat pump or power is cut then
restored, the unit will not start for 2 minutes to protect the compressor
Defrosting Function
When the fan coil unit temperature reaches 0°C, the hot discharge
bypass defrosting mode will operate for 15 minutes or until the
evaporator temperature reaches 5°C.
Protection Systems
The heat pump has protection systems that will stop the operation of the
unit if:
Suction pressure drops due to refrigerant charge loss or air ow blockage
Over pressure (551 Psi) or over temperature (110°C) in the refrigerant
system
SPECIFICATIONS
SPECIFICATIONS