CONNECTING ELECTRIC DRYERS (continued)
WARNING:
Connect the power cord to the terminal block. Connect
each power cord wire to the termlnal block screw that
has the same colored wire. For example, connect the
black power cord wire to the terminal block screw
with the biack wire. Failure to follow these instructions
may result in o short, overload, fire or death.
Four-Wire Power Cord
e A 4-wlre connection is reAulred for all
mobile and manufactured home in_allafionsr
as well as all new construction offer
Jonua_ 1, 1996.
A UL-listed strain relief is required.
Use a 30.amp, 240-volt_ 4-wlre, UL-listed power cord
with #10 AWG-mlnlmum copper conductor and closed
loop or forked terminals with upturned ends.
?
Terminal
Block
4 Wire
Power
__ Cord
O Remove the terminal block access cover on the upper
back o_ the dryer.
Install a UL-listed strain relief into the power cord
through-hole.
Thread a 30-amp, 240-volt, 4-wireo UL-listed power
cord with #10 AVCG-minimum copper conductor
through the strain relief.
Green Ground
'Neutral
Green Wire Grounding
Power Cord _ _--_ Wire
O Transfer the neutral grounding wire from behind the
green ground screw to the center screw of the terminal
block.
Attach the two hot leads (black and red) of the power
cord to the outer terminal block screws.
Attach _he power cord white neutral wire to the cen-
ter screw of the terminal block.
Attach the power cord ground wire to the green
ground screw.
TIGHTEN ALL SCREWS SECURELY.
O Reinsta I the terminal block access cover.
Grounding through the neutral wire is prohibited for: (1)
new branch-circuff instaffations, (2) mobile homes, (3)
recreo|ionoi vehicles, and (4) areas where local codes
prohibit grounding through fhe neutral wire.
Three-Wire Power Cord
. A 3-wire connectlon is NOT permiffed on
new construcflon after January 1, 1996.
* A UL-listed strain relief is required.
Use a 30-amp0 240-voff0 3-wire, UL-listed power cord
with #10 AWG-minimum copper conductor and closed
loop or forked terminals with upturned ends.
?
Terminal
Block
UL-Listed
Relief
JL-Listed
Power
Cord
Remove the terminal block access cover on the upper
back of _he dryer.
Install o UL-listed strain relief into the power cord
throug h=hole.
Thread a 30-amp_ 240-voff0 3-wire, UL-listed power
cord with #10 AWG-minimum copper conductor
through the strain relief.
Neutral ___
-Grounding-- H,_ -_-_l Hot
- Wire ............. (Red)
Green Ground
External Ground
g
@
@
@
@
Attach the two hot leads {block and red) of the
power cord to the outer terminal block screws.
Attach the power cord neutral (white) wire to the center
termina! btock screw.
Connect the external ground (if required by local
codes) to the green ground screw.
TIGHTEN ALL SCREWS SECURELY.
Reinstall the terminal block access coven
13