PIPING INSTALLATION
Indoor Condensate Drain Piping (con’t)
Completing Condensate Drainage Piping
• Include the exterior section of condensate hose in the pipe/wire bundle.
• Fasten the refrigerant and condensate pipe assembly to the exterior
wall for support.
• The drain pipe should terminate 6 inches above grade.
Test the Condensate Drainage Piping
• Find the drainage port with the air inlet grille and right side panel removed.
• Slowly add 20 to 24 oz. of water to the drain pan as shown below.
• Water must drain freely from the unit If not, check the pipe slope or see if there are any pipe restrictions.
• Verify all piping joints are leak free.
13