AR49 Arctic Air Standard Reach In Solid Door Heavy Duty Refrigerator

User Manual - Page 8

For AR49.

PDF File Manual, 20 pages, Read Online | Download pdf file

AR49 photo
Loading ...
Loading ...
Loading ...
8
Installation, Operation & Maintenance Manual
REACH-IN REFRIGERATORS AND FREEZERS
OPERATION
Refrigeration Cycles
Refrigerators
The evaporator fans run continuously during the refrig-
eration cycles to maintain the factory set internal tem-
perature range at 34°F to 38°F. The door switch turns
on the lights when the door is opened.
1. Every 6 hours, the unit turns off and the controller
displays the defrost symbol this allows the evapora-
tor coil to clear the ice. When the coil temperature
reaches 41°F (or after 20 minutes) the unit re-starts.
2. The anti-condensation heaters (located on the door
frames) work in conjunction with the compressor.
Freezers
The controller provides power to the condensing unit
and the evaporator fans during the refrigeration cycles
to maintain the factory set internal temperature range
at -3°F to -7°F. The evaporator fans run whenever the
evaporator coil temperature is below 35°F, except during
the defrost cycle when they cycle off. The door switch
turns on the lights when the door is opened.
1. Every 6 hours, the unit turns off and the controller
displays the defrost symbol this allows the evapora-
tor coil to clear the ice. When the coil temperature
reaches 45°F (or after 20 minutes) the unit re-starts.
2. The anti-condensation heaters (located on the door
frames) work in conjunction with the compressor.
On/Off Switch
The on/off switch is located on the front of the top shroud.
When the unit is on, the green LED is on.
Front Panel Controls and Indicators
The front panel controls and indicators are used to set
and display the unit functions and status.
1
1a
8a
3a2a
2
8 7
4 5
6
3
Callout
No.
Control /
Indicator
Function
1 Fan Indicates the fans are running.
2 Defrost
Press to start the manual defrost
cycle.
3 Compressor
Indicates the compressor is
running.
4 Up Arrow
To display the last temperature
alarm.
In programming mode it
browses the parameter codes or
increases the displayed value.
5 Down Arrow
To display the last temperature
alarm.
In programming mode it
browses the parameter codes or
decreases the displayed value.
6 SET
Used to display a target set
point; in programming mode it
elects a parameter or conrm an
operation.
7 Display
Indicates the room temperature,
the set points and the alarm
codes.
8 Alarm Indicates a temperature alarm.
Key combinations are used to perform functions that
cannot be performed with a single key.
Key Combinations
Press Keys Result
Up Arrow Down Arrow
Locks and unlocks the
keyboard.
SET Down Arrow
Enters the programming
mode.
SET Up Arrow
Returns to the room
temperature display.
The LED functions display operational conditions.
Callout No. Mode LED Function
1a
On Fans enabled
Flashing
Fans delay after defrost
in progress
2a
On Defrost enabled
Flashing
-Programming phase
(ashing with “icon”)
- Drip time in progress
3a
On Compressor enabled
Flashing
-Programming phase
(ashing with “icon”)
-Anti-short cycle delay
enabled
8a On
A temperature alarm
happened
Loading ...
Loading ...
Loading ...