Movincool CPK63 Portable Air Conditioner Cooling Area,

User Manual - Page 75

For CPK63.

PDF File Manual, 79 pages, Read Online | Download pdf file

CPK63 photo
Loading ...
Loading ...
Loading ...
MODEL NAME CLIMATE PRO K60 CLIMATE PRO K63
Electronic Features Control Programmable Programmable
Cooling Capacity
Rating Conditions: 95°F, 60% RH
60,000 Btu/h 60,000 Btu/h
Electrical
Characteristics
Voltage Requirement 208/230V, 1Phase, 60Hz 460V, 3Phase, 60Hz
Total Power Consumption 6.6 kW 6.6 kW
Current Consumption
33.6/31.5 amps 12.2 amps
Recommended Fuse Size 50 amps 20 amps
NEMA Plug Confi guration 6-50P L16-20
Min. - Max. Voltage 198 -253 440 -480
Fans: Motor Output
Evaporator 0.56 kW 0.56 kW
Condenser 0.3 kW x 2 motors 0.3 kW x 2 motors
Evaporator
Fan Type Centrifugal Centrifugal
Max. Air Flow (hi/mid/low) 1770/1710/1650 CFM 1770/1710/1650 CFM
Max. External Static Pressure 0.9 IWG 0.9 IWG
Condenser
Fan Type Centrifugal Centrifugal
Max. Air Flow (hi) 2400 CFM 2400 CFM
Max. External Static Pressure 0.85 IWG 0.85 IWG
Compressor
Type Hermetic Rotary Hermetic Rotary
Output 3.45 kW 3.45 kW
Refrigerant Type R-410A R-410A
Dimensions W x D x H 31 x 55 x 64 in 31 x 55 x 64 in
Weight Net / Shipping
582/666 lb 659/743 lb
Power Cord
Gauge 6 AWG (3-core) 12 AWG (4-core)
Length 6  6
Condensate Tank Capacity Auto Pump Included Auto Pump Included
Operating
Conditions
Min. 65°F (@ 50% RH) 65°F (@ 50% RH)
Max. 105°F (@ 50% RH) 105°F (@ 50% RH)
Max. Duct Length
Per Cold Duct Hose 40  40
Hot Duct Hose 100  100
Max. Sound Level
With Duct (hi/mid/low) 69/68/67 dB(A) 69/68/67 dB(A)
Without Duct (hi/mid/low) 71/70/69 dB(A) 71/70/69 dB(A)
75
TECHNICAL SPECIFICATIONS
Specifi cations are subject to change without notice.
Loading ...
Loading ...
Loading ...