Kidde 21027683 10 Year Sealed-In Battery Powered Interconnected Combination Carbon Monoxide and Photoelectric Smoke Alarm

User Manual - Page 2

For 21027683.

PDF File Manual, 2 pages, Read Online | Download pdf file

21027683 photo
Loading ...
10-Year Sealed Battery Powered Combo
Smoke/CO Alarm with Wire-Free Interconnect
Model P4010DCSCO-W
Architectural and Engineering
Specifications
The smoke/CO alarm model shall be P4010DCSCO-W or approved equal and
is powered by non-replaceable lithium metal batteries with 10-year life.
The lithium batteries shall be sealed in the unit to prevent removal and/or
tampering. The unit shall incorporate a photoelectric smoke sensor and an
electrochemical CO sensor.
The alarm can be installed on the surface of any wall or ceiling following the UL/
Manufacturer’s approved placement guidelines. The alarm shall incorporate an
activation switch that can be engaged with the included tool or screwdriver to
power on the alarm at startup, and deactivate the alarm at end of alarm life.
The P4010DCSCO-W shall include a test button that will simulate fire and
carbon monoxide conditions and cause the unit to go into alarm. This sequence
tests the unit’s electronics to ensure proper operation.
The unit shall have audible methods for warning of smoke or fire danger: a
piezoelectric horn, rated at 85 decibels at 10 feet, and a voice warning. In a
smoke incident, the horn will sound in the repetitive manner – three long beeps,
a 1.5 second pause, three long beeps, repeating. In between, the unit will
announce a voice warning, “Fire!” For a CO incident, the horn will sound in the
repetitive manner - 4 quick beeps, voice message “Warning! Carbon Monoxide”,
4 quick beeps. The red LED ring will flash in conjunction with the alarm sound.
The unit shall incorporate wireless alarm interconnect capability, whereas when
one interconnected unit sounds an alarm, all other compatible wireless units in
the wireless alarm network will alarm. The maximum distance between wireless
interconnect models is greater than 300 feet in open air. The alarm interconnect
shall be supervised, where an audible and visual indication is given if the alarm
loses connection to other units in the network.
A maximum of 24 Kidde Safety devices may be interconnected in a multiple
station arrangement. The interconnect system should not exceed the NFPA
interconnect limit of 12 smoke alarms and/or 18 alarms total (smoke, CO,
Smoke/ CO Combination, heat, etc.). With 18 alarms interconnected, it is still
possible to interconnect up to a total of 6 remote signaling devices and / or relay
modules.
The unit shall at a minimum meet the requirements of UL217, UL 2034, NFPA 72,
The State of California Fire Marshall, NFPA101 (One and two family dwellings),
Federal Housing Authority (FHA), Housing and Urban Development (HUD). The
alarm shall be UL Listed and shall include a 10-year manufacturer’s limited
warranty.
Ordering Information
Technical Specifications
Model: P4010DCSCO-W
Power Source: Sealed Lithium Batteries
Sensor: Smoke: Photoelectric
CO: Electrochemical
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 10 to 95% non-condensing
relative humidity (RH)
Size: 5.59” in diameter x 1.91” depth
Weight: 0.6 lb
Interconnects: Up to 24 Kidde devices
Warranty: 10 year limited
5.59"
1.91"
5.10"
1016 Corporate Park Drive
Mebane, NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-P4010DCSCO-W sheet rev. 10-2017
Compatible Intelligent Wire-Free 10-Year Models
10-Year Sealed Battery Operated Alarms
P4010DCS-W: Smoke Alarm with Wire-Free Interconnect
P4010LDCS-W: Smoke Alarm with Wire-Free Interconnect and Emergency Safety Light
P4010DCSCO-W: Combination Smoke and CO Alarm with Wire-Free Interconnect
HARDWIRED Alarms with 10-Year Sealed Battery Backup
P4010ACS-W: Smoke Alarm with Wire-Free Interconnect
P4010LACS-W: Smoke Alarm with Wire-Free Interconnect and Emergency Safety Light
P4010ACSCO-W: Combination Smoke and CO Alarm with Wire-Free Interconnect
Leading authorities recommend that both ionization and photoelectric smoke alarms be installed to help ensure maximum detection of the various types of fires
that can occur within the home. Ionization sensing alarms may detect invisible fire particles (associated with fast flaming fires) sooner than photoelectric alarms.
Photoelectric sensing alarms may detect visible fire particles (associated with slow smoldering fires) sooner than ionization alarms.
Ordering No: UPC I 2 of 5
Pack
Cong.
Pack
Qty
Dimensions
(w” x d” x h”) Weight
Cartons/
Pallet
21027311 0-47871-27311-9 100-47871-27311-6 Single
2
8.25 x 6.25 x 9.5 2.5 136
21027680 (Red Cross) 0-47871-27311-9 100-47871-27311-6 Single
2
8.25 x 6.25 x 9.5 2.5 136