Loading ...
Loading ...
Loading ...
en Important safety information
12
Adequate incoming air must therefore
always be ensured.
An incoming/exhaust air wall box alone will
not ensure compliance with the limit.
Safe operation is possible only when the
partial vacuum in the place where the heat-
producing appliance is installed does not
exceed 4 Pa (0.04 mbar). This can be
achieved when the air needed for combustion
is able to enter through openings that cannot
be sealed, for example in doors, windows,
incoming/exhaust air wall boxes or by other
technical means.
In any case, consult your responsible Master
Chimney Sweep. He is able to assess the
house's entire ventilation setup and will
suggest the suitable ventilation measures to
you.
Unrestricted operation is possible if the vapour
extractor hood is operated exclusively in the
circulating-air mode.
:Warning – Danger of death!
Risk of poisoning from flue gases that are
drawn back in. If installing a ventilation system
in a room with a heat-producing appliance
connected to a chimney/flue, the electricity
supply to the hood must be equipped with a
suitable safety switch.
:Warning – Risk of injury!
Components inside the appliance may have
sharp edges. Wear protective gloves.
Risk of injury!
The appliance may fall down if it has not
been properly fastened in place. All
fastening components must be fixed firmly
and securely.
Risk of injury!
The appliance is heavy. To move the
appliance, 2 people are required. Use only
suitable tools and equipment.
Risk of injury!
Changes to the electrical or mechanical
assembly are dangerous and may lead to
malfunctions. Do not make any changes to
the electrical or mechanical assembly.
:Warning – Risk of electric shock!
Components inside the appliance may have
sharp edges. These may damage the
connecting cable. Do not kink or pinch the
connecting cable during installation.
Risk of electric shock!
It must always be possible to disconnect
the appliance from the power supply. The
appliance must only be connected to a
protective contact socket that has been
correctly installed. If the plug can no longer
be reached after installation, an energy-
isolating device in the phases must be
provided in the permanent electrical
installation in accordance with the
installation regulations. The permanent
electrical installation must only be wired by
a professional electrician. We recommend
installing a residual-current circuit breaker
(RCCB) in the appliance's power supply
circuit.
:Warning – Risk of electric shock!
Incorrect repairs are dangerous. Repairs may
only be carried out and damaged power
cables replaced by one of our trained after-
sales technicians. If the appliance is defective,
unplug the appliance from the mains or switch
off the circuit breaker in the fuse box. Contact
the after-sales service.
:Warning – Danger of suffocation!
Packaging material is dangerous to children.
Never allow children to play with packaging
material.
Loading ...
Loading ...
Loading ...